Door Sensor (Obtained locally)
When connected, the door sensor will detect
when the door in the room was opened or
closed. This feature must be used in conjunction
with the motion sensor.
The door and motion sensors work together
to automatically turn the unit ON or OFF.
Door Sensor
External Fan (Obtained locally)
When connected, an auxiliary or external fan
can be controlled with the indoor fan motor
on the Zoneline. Connections provide 24 V AC
to energize a remote relay, turning on the
external fan.
External Fan
Central Desk Control
When connected, the unit can be turned ON
or OFF with a switch located at the Central
Control Panel. A separate wire pair must be
run from each separate controlling switch to
each individual Zoneline.
Central Desk Control
Remote Thermostat
When connected, the unit will be controlled
by a remote thermostat.
NOTE:
The number 4 dip switch must be in the
enabled
(UP)
position to activate the remote
thermostat. (See the installation instructions
supplied with the remote thermostat).
IMPORTANT:
The Zoneline thermostat connections
provide 24 V AC only.
If using a digital/electronic wall thermostat,
you must set it to the 24 V AC setting.
See the Installation Instructions for the
wall thermostat.
CAUTION:
Damage to a wall thermostat or to the
Zoneline electronics can result from improper
connections. Special care must be used in
connecting blue and black wires. No line voltage
connections should be made to any circuit.
Isolate all wires in building from line voltage.
Common - Ground
White - Heater
Yellow - Compressor
Black - Solenoid
Green - High Speed Fan
Green - Low Speed Fan
Red - 24 V AC only