Calculations
A.2
FireShield Technical Reference Manual
Form A
Module
Quantity
Standby
current
(mA)
Qty
×
Standby
current (mA)
Alarm
current
(mA)
Qty
×
Alarm
current (mA)
FSRSI [1]
12
48
FSRZI-A [1]
8
35
FSRRM common [1]
30
41
FSRRM zone [1]
8
65
Other AUX
Total AUX [5] [6]
Form B
(
Note:
Calculate IDC detector load or use maximum load.)
IDC
Quantity of
detectors [2]
Detector current
(mA) [3]
Total standby current [4]
(quantity x current in mA)
IDC1
IDC2
IDC3
IDC4
IDC5
IDC6
IDC7
IDC8
IDC9
IDC10
Total current for all IDCs =
Max IDC standby current: FS302 = 4.5 mA, FS502 = 7.5 mA, and FS1004 = 15.0 mA
Notes
[1] Use of FSRSI, FSRZI-A, and FSRRM is limited as follows: Three- and five-zone panels support 2 FSRSIs, 2 FSRZI-As, and 4
FSRRMs, ten-zone panels support 2 FSRSIs, 4 FSRZI-As, and 6 FSRRMs.
[2] See the FireShield UL and ULC Compatibility List (P/N 3100468) for the maximum number of detectors per IDC.
[3] See FireShield UL and ULC Compatibility List (P/N 3100468) for detector current ratings.
[4] Maximum current per IDC may not exceed 1.5 mA.
[5] Aux power supplied by panel cannot exceed 0.5 A. If more than 0.5 A is required, you must use a compatible UL/ULC listed
fire alarm power supply.
[6] When using an auxiliary power supply, you must connect the -24 OUT connection on the panel to the negative connection on
the auxiliary power supply. Refer to the installation section for more information.
Содержание FireShield FS1004
Страница 1: ...FireShield Technical Reference Manual P N 3100353 Rev 3 0 12MAY03 ...
Страница 10: ...System overview and operation 1 8 FireShield Technical Reference Manual ...
Страница 40: ...Programming 3 18 FireShield Technical Reference Manual ...
Страница 42: ...Maintenance 4 2 FireShield Technical Reference Manual ...
Страница 60: ...Panel specifications D 2 FireShield Technical Reference Manual ...
Страница 66: ...Index Z 4 FireShield Technical Reference Manual ...
Страница 68: ......