Installation
FireShield Technical Reference Manual
2.11
Connecting a CTM module
The CTM4.7 City Tie Module is an interface between the
control panel notification appliance circuit and a master box. It
provides off-premises signal transmission for systems that
must comply with NFPA requirements for Auxiliary
Protective Systems. The CTM4.7 activates a local energy fire
alarm box, which provides a 24 Vdc alarm signal (current
limited at 200 mA). The 4.7 K
Ω
end of line resistor required
by the NAC is built in to the CTM4.7.
Requirements
When connecting a CTM to the panel, the following hardware
and programming requirements must be met:
•
The NAC used must be dedicated to CTM use only
•
All alarm zones must be programmed to activate the
dedicated NAC
•
The NAC used must not be programmed for Signal
Silence
Specifications
Power: Nominal 24 Vdc @ 200 mA
Municipal box operation: Nominal 24 Vdc
Maximum wiring resistance: 25
Ω
Trip current: 200 mA into 14.5
Ω
coil
Maximum current: 300 mA
Standby current: 20 mA
Mounting: Single gang box
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing
The following are wiring diagrams showing how the polarity
switches during an alarm condition.
Panel in normal condition
Notification
appliance circuit
1
1
2
2
CTM4.7
+
+
+
+
_
_
_
_
[1] [2]
Master box
Municipal circuit
Normal condition
[3]
[4]
[5]
Panel in alarm condition
Notification
appliance circuit
1
1
2
2
CTM4.7
+
+
+
+
_
_
_
_
[1] [2]
Master box
Municipal circuit
Alarm condition
[3]
[4]
[5]
Notes
[1] 200 mA into a 14.5
Ω
trip coil max., loop resistance = 25
Ω
[2] This circuit is nonpower-limited and is supervised for
grounds and opens, but not shorts
[3] Supervised and power-limited
[4] NAC must be programmed for continuous signal
[5] CTM4.7 must be mounted in the same room as the panel
Содержание FireShield FS1004
Страница 1: ...FireShield Technical Reference Manual P N 3100353 Rev 3 0 12MAY03 ...
Страница 10: ...System overview and operation 1 8 FireShield Technical Reference Manual ...
Страница 40: ...Programming 3 18 FireShield Technical Reference Manual ...
Страница 42: ...Maintenance 4 2 FireShield Technical Reference Manual ...
Страница 60: ...Panel specifications D 2 FireShield Technical Reference Manual ...
Страница 66: ...Index Z 4 FireShield Technical Reference Manual ...
Страница 68: ......