1200C-2000C Fire Alarm Control Panel and Repeater User Manual 

LED indicator 

Description 

Disable 

A yellow LED indicates that one or more of the following is disabled: 

•  Devices on the loop 
• Area 
• Zone 
• Sounders 
• Fire 

brigade· 

• Any 

delays 

ON

 

Supply fault 

A yellow LED indicates one or more of the following supply faults: 

•  A mains failure 
•  A battery problem (battery disconnected or not charging) 
•  An earth fault

 

A yellow LED indicates one or more of the following: 

System fault 

•  Internal memory failure 
• Clock 

failure 

•  Watchdog time out 
• Tamper 

switch 

• Service 

switch 

• Logic 

error 

• Memory 

lock 

•  No checksums calculated 
•  Hardware test fault 
•  Fireman’s' panel down 
• Repeater 

down

 

• Panel 

down 

•  Global repeater down 
• Input 

fault 

• Output 

fault 

• Configuration 

fault 

• Checksum 

fault 

•  Protected memory overwritten 
• Time 

date 

wrong 

• Access 

fault 

• FEP 

fault 

• Watchdog 

time-out

 

Processor running 

A flashing green LED indicates normal operation 

Supply on 

A steady green LED indicates that the control panel is powered up 

 

Содержание 1200C

Страница 1: ...GE Security P N 1068369 REV 7 0 ISS 03JUN09 1200C 2000C Fire Alarm Control Panel and Repeater User Manual ...

Страница 2: ...s Intended use Use this product only for the purpose it was designed for refer to the data sheet and user documentation for details For the latest product information contact your local supplier or visit us online at www gesecurity eu Certification and compliance European Union directives 2002 96 EC WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste i...

Страница 3: ...ser interface controls 2 General indicators 4 Controls buttons and indicators 6 Sounder buttons and indicators 7 Fire brigade buttons and indicators 8 Repeater buttons and indicators 9 Zone indicators 10 Operation 11 Panel operation in standby 11 Panel operation in fire alarm 12 Panel operation in pre warning 13 Panel operation in fault 14 Maintenance 15 Fire alarm system maintenance 15 Battery ma...

Страница 4: ...ing this product contact your installation or maintenance contractor Limitation of liability Installation in accordance with this manual applicable codes and the instructions of the authority having jurisdiction is mandatory GE Security shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failu...

Страница 5: ...el interface indicators and controls The control panel interface Figure 1 The control panel interface 1 LCD screen 2 Alphanumeric keypad 3 Fire brigade buttons and indicators 4 Key switch 5 Sounder buttons and indicators 6 Repeater buttons and indicators 7 Controls buttons and indicators 8 Zone indicators 9 General indicators ...

Страница 6: ...itch in any position User interface controls The user interface has 20 buttons 10 of which are alphanumeric The remaining 10 are described below Table 2 Description of the control panel user interface controls Button Description Alpha selection when using the alphanumeric buttons Display the most recent alarm Print the current screen Scroll between Alarm Fault and Conditions View additional inform...

Страница 7: ...1200C 2000C Fire Alarm Control Panel and Repeater User Manual 3 Button Description Increase a value Decrease a value ...

Страница 8: ...LED 5 System fault LED 6 Processor running LED 7 Supply On LED Table 3 Description of general indicators LED indicator Description Fire Alarm Two red LEDs indicate a fire alarm Fault A yellow LED indicates one or more of the following general faults Device fault Supply fault Processor fault Bell fault Communications fault Fire brigade fault Any test mode Any disablement ...

Страница 9: ...n earth fault A yellow LED indicates one or more of the following System fault Internal memory failure Clock failure Watchdog time out Tamper switch Service switch Logic error Memory lock No checksums calculated Hardware test fault Fireman s panel down Repeater down Panel down Global repeater down Input fault Output fault Configuration fault Checksum fault Protected memory overwritten Time date wr...

Страница 10: ...on The buzzer sound is Constant for a fire alarm Fast intermittent for a fault warning Slow intermittent for a condition warning Press the Silence Buzzer button to silence the buzzer A steady yellow LED indicates that the buzzer has been silenced Reset Enabled Press this button to reset the fire panel Disable Enabled Press this button to display the Disable menu on the LCD screen The yellow LED in...

Страница 11: ... LED indicator Key switch position Description Sound A red LED indicates that the sounders are activate sounding Delay ON OFF A single LED indicates that the sounder delay has been toggled ON or OFF Fault Disable Enabled Press the Fault Disable button to disable the sounders The LED flashes when a fault is detected and is steady when the sounders are disabled Silence Enabled A yellow LED indicates...

Страница 12: ...l Enabled Push this button to activate the fire brigade notification A red LED indicates that a signal has been sent Delay ON OFF The LED indicates that the fire brigade delay has been toggled ON or OFF Fault Disable Enabled Push this button to disable the fire brigade notification The LED is steady when the feature is disabled and flashes when a fault is detected Stop Fire brigade Enabled Push th...

Страница 13: ... to be emulated 3 Press the Enter button To stop emulation 1 Press the Panel button 2 Press 0 3 Press the Enter button When a global repeater is emulating a panel it is not necessary to stop emulation before emulating another panel The global repeater will automatically stop the emulation before trying to emulate another panel Local repeater Press the Panel button to start emulating the panel Emul...

Страница 14: ...al Zone indicators Each zone has two LED indicators A red LED indicates a fire alarm and a yellow LED indicates a fault The zone fault LED flashes when there is a fault and remains steady if the entire zone has been disabled Figure 7 Zone fire and fault indicators ...

Страница 15: ... LED is steady when a delay is running This is logged as a condition Press the SILENCE BUZZER button to silence the internal buzzer All other LEDs OFF Figure 8 System Status menu normal operation X Î SYSTEM STATUS Fri 12 10 04 09 17 37 Site text up to 40 characters Y Î Site text up to 40 characters Z Î Scanning Day Mode Zones on E Î Î Alarm 0 Faults 0 Cond 0 P 1 SDZ 1 Menu title date and time 2 Si...

Страница 16: ...ore than one fire alarm exists use the up and down arrows to view each alarm 4 Press Silence Buzzer to silence the internal buzzer and to acknowledge the alarm 5 Once the evacuation of the building is complete silence the sounders by turning the enable disable key switch to enable see Key switch on page 2 6 Press the Silence button The yellow Silence LED is steady 7 If you need to restart the evac...

Страница 17: ...xample shown above the pre alarm is in zone 6 area 1 at address 12 in loop 1 2 If more than one pre warning exists use the up and down arrows to view each pre warning condition 3 Press Silence Buzzer to silence the internal buzzer and to acknowledge the pre warning 4 Investigate the cause of the pre warning condition 5 When the pre warning condition is under control turn the enable disable key swi...

Страница 18: ...ls A specific zone has been placed in test mode The fault remains until the test is complete Fault Disable Sounders The sounders are disabled or there is a fault with the connection Enable the sounders If the fault continues check the connections Fault Disable Fire brigade The fire brigade notification has been disabled or there is a fault with the connection Enable the Fire brigade notification I...

Страница 19: ...has received attention Quarterly Check the log book entries and ensure that any necessary action has been taken Check the state of the batteries and corresponding connections Visually inspect the control panel for signs of moisture and other deterioration Test the alarm fault and ancillary functions of the fire panel Yearly Carry out the recommended daily and quarterly inspection and test routines...

Страница 20: ...he panel That the control panel event log does not indicate a mains failure in the last twenty four hours If the leads are in good condition all connections are correct and the control panel continues to report that the test has failed twenty four hours after the last mains failure then the batteries should be replaced immediately Replacing batteries To replace the batteries 1 Disconnect and remov...

Страница 21: ... to fire protection equipment 7 11 Delay to output 7 12 Dependency on more than one alarm signal 7 13 Alarm counter 8 4 Total loss of the power supply 9 5 Disablement of addressable points 10 Test EN 54 2 compliance for control panels with the VDS2000 module Control panels with the VDS2000 module installed have the following options with requirements according to EN 54 2 Table 11 EN 54 2 options w...

Страница 22: ...uptmelder interface to EMZ Construction Products Directive CPD Details of the CPD certification for 1200C 2000C fire panels and global repeaters are shown below Table 12 CPD certification for 1200C 2000C series fire panels and global repeaters Certification Certification body 1134 Certificate number 1134 CPD 069 Manufacturer GE Security B V Kelvinstraat 7 6003 DH Weert The Netherlands ...

Страница 23: ...1200C 2000C Fire Alarm Control Panel and Repeater User Manual 19 ...

Страница 24: ......

Отзывы: