1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Panel operation in fault
The internal buzzer sounds to indicate a fault.
1. Press the
Silence Buzzer
button to silence the internal buzzer.
2. The yellow
Fault
LED is steady to indicate a fault in the fire system.
3. The yellow fault LED for the corresponding feature or device is also steady.
Table 9: Fault LED indications
LED indication
Action required
A specific zone
Call the maintenance engineer.
Disable
A zone, loop, or device has been disabled.
Supply fault
Check the mains supply and battery.
System fault
Call the maintenance engineer.
Test (Controls)
A specific zone has been placed in test mode. The fault remains until
the test is complete.
Fault/Disable (Sounders)
The sounders are disabled or there is a fault with the connection.
Enable the sounders. If the fault continues, check the connections.
Fault/Disable (Fire brigade)
The fire brigade notification has been disabled or there is a fault with
the connection, Enable the Fire brigade notification. If the fault
continues, check the connections.
Fault details are also displayed on the LCD screen. The figure below shows a
communication fault in zone 6, area 1 at address 12 in loop 1 (the fault is in a specific
zone).
Figure 11: The alarm screen (fault)
ALARM:
1
Event:
79
Active
Zone:
6
Area:
1 ALMLVL
Address:
1/12
Communication fault
MCP
06/02/05 09:39:34
(Site text – up to 40 characters)
¿À
X
Alarm:
0
Faults:
1
Cond.:
0
P:
1 SDZ