CHAPTER 3: FIELDBUS INTERFACE
PROFIBUS DP
MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
3-3
Figure 3-1: Comms board power supply configuration
NOTE
NOTE:
Other switch combinations are NOT ALLOWED.
Profibus termination
Profibus segments should be terminated by a bus termination. The MM200 termination
voltage is +5V and the connections are as follows:
Figure 3-2: Profibus termination
If the bus voltage level is higher, such as 24V, an external device must be used to drop the
voltage to the re5V termination level. The Procentec T1 Terminator or equivalent is
suitable to provide proper termination to the MM200 from a 24V level.
Profibus DP-parameterization
The MM200 relay supports mandatory parameterization. The relay keeps its user
parameter data / setpoints in non-volatile memory and does not need device related
parameterization during startup of the DP master. The EnerVista MM200 Setup software is
the best tool for user parameterization of the MM200 device.
Protocol Options
SW1
SW2
SW3
SW4
DeviceNet
ON
ON
OFF
OFF
Profibus
OFF
OFF
ON
ON
Supply Options
SW5
SW6
SW7
SW8
Internal
ON
ON
OFF
OFF
External
OFF
OFF
ON
ON
INTERNAL
SUPPLY
EXTERNAL
SUPPLY
ON
ON
888845A1.CDR
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
= switch position
888847A1.CDR
+5V
Line B
Line A
Data ground
390
220
390
Ω
Ω
Ω