5-142
L60 Line Phase Comparison System
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
5.5.3 PHASE COMPARISON ELEMENTS
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS
PHASE COMPARISON ELEMENTS
b) 87PC SCHEME
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE COMPARISON ELEMENTS
87PC SCHEME
PHASE COMPARISON
ELEMENTS
87PC SCHEME
MESSAGE
ADVANCED
FAULT DETECTORS
MESSAGE
CHARGE CURRENT
COMPENSATION
MESSAGE
OPEN BREAKER
ECHO
87PC SCHEME
87PC FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
87PC SCHEME SELECT:
2TL-TR-SPC-2FC
Range: 2TL-TR-SPC-2FC, 2TL-BL-SPC-2FC,
2TL-TR-DPC-3FC, etc.
MESSAGE
87PC BLOCK:
Off
Range: FlexLogic operand
MESSAGE
87PC SIGNAL SOURCE:
One Source Current
Range: One Source Current, Two Sources Current
MESSAGE
87PC SIGNAL:
Mixed I_2-K*I_1
Range: Mixed I_2–K*I_1, Mixed I_1+I_2/K, 3I_0
MESSAGE
87PC MIXED SIGNAL K:
0.20
Range: 0.00 to 0.25 in steps of 0.01
MESSAGE
87PC MIXED SIGNAL
REF ANGLE: 0°
Range: 0 to 359° in steps of 1
MESSAGE
87PC FDL PICKUP:
0.50 pu
Range: 0.02 to 15.00 pu in steps of 0.01
MESSAGE
87PC FDL AUX:
Off
Range: FlexLogic operand
MESSAGE
87PC FDH PICKUP:
0.75 pu
Range: 0.05 to 15.00 pu in steps of 0.01
MESSAGE
87PC FDH AUX:
Off
Range: FlexLogic operand
MESSAGE
87PC FDH SUPV:
Off
Range: FlexLogic operand
MESSAGE
87PC CH1 ASYMMETRY:
0.0 ms
Range: –5.0 to 5.0 ms in steps of 0.1
MESSAGE
87PC CH2 ASYMMETRY:
0.0 ms
Range: –5.0 to 5.0 ms in steps of 0.1
MESSAGE
87PC CH1 DELAY:
0.0 ms
Range: 0.0 to 30.0 ms in steps of 0.1
Содержание L60
Страница 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 100: ...3 42 L60 Line Phase Comparison System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Страница 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...