Shift fixtures until keyhole tabs lock in place and
fixtures are horizontally aligned.
Install two #8-32 screws with nuts (provided) to
fasten the end plates of the joined fixtures together.
Continue to add fixtures as needed to complete
the continuous run.
Note:
If there are unused quick-connectors at the
end of a run, cut off the connectors and cap the
ends with wire connectors to terminate the wires.
Replace open end plate with a solid end plate.
Note:
The current though the continuous fixture run
cannot exceed 20A. See maximum fixture run length
listed below.
Output
Voltage
Total Run Length (ft.)
T
H
V
120V
369
234
164
208V
640
406
284
277V
852
540
379
347V
1028
646
463
480V
1239
835
635
Troubleshooting
Symptom
Solution
Luminaire will
not turn on
• Check that the color of the supply side wires match the color of the wires they are connected to.
• Check that all wire connectors are properly connected.
• Verify that your input voltage is within specs.
• If you are using any additional controls (i.e. wireless controls or motion sensors), please
also verify that those are working properly and that the unit is setup to interface with the controllers.
Mounting bracket slides
from side to side
• Check that the mounting bracket is properly tightened using the adjustment screws provided.