7–104
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
CHAPTER 7: TESTING
7.6.2
Ground Alarm And Trip
1.
Alter the following setpoints:
S2: SYSTEM SETUP\CT INPUTS\GROUND SENSING:
RESIDUAL
S2: SYSTEM SETUP\CT INPUTS\PHASE CT PRIMARY:
100
S4: PROTECTION\GROUND CURRENT\GROUND TRIP:
TRIP
S4: PROTECTION\GROUND CURRENT\GROUND PRIMARY TRIP PICKUP:
80%
S4: PROTECTION\GROUND CURRENT\GROUND ALARM:
MOMENTARY
S4: PROTECTION\GROUND CURRENT\GROUND PRIMARY ALARM
PICKUP:
40%
2.
While viewing
A2: METERING\CURRENT\GROUND CURRENT
, begin injecting
current into the 5A ground input. The ALARM LED will become lit and the alarm relay
will change state at one half the trip setting; i.e. at a displayed Ground Fault current of
40 A (40% of
PHASE CT PRIMARY
setting).
3.
With the display showing GROUND ALARM message, change the display to
A2:
METERING\ CURRENT\GROUND CURRENT
and continue increasing the input
current. When the display current of 80 A (80% of
PHASE CT PRIMARY
) is reached,
the 239 trip relay will activate and the TRIP LED will become lit. The 239 will display
CAUSE OF LAST TRIP: GROUND FAULT message.
4.
Turn the ground current off and press the reset key to reset the trip relay.
Содержание Multilin 239
Страница 6: ...TOC 4 369 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 20: ...1 14 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 1 OVERVIEW ...
Страница 48: ...3 10 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Страница 96: ...4 58 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 4 PROGRAMMING ...
Страница 108: ...5 70 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 5 MONITORING ...
Страница 149: ...CHAPTER 7 TESTING 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL 7 111 FIGURE 7 2 239 Hardware Block Diagram ...
Страница 150: ...7 112 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING ...
Страница 152: ...A 2 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER A ...