7–102
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
CHAPTER 7: TESTING
EXAMPLE: CALCULATING THE PERCENT OF UNBALANCE
Find the percent unbalance given the following information:
The average of the three phase currents is:
Now, since
I
av
<
I
FLC
, we have percent unbalance given by:
Therefore, the percent unbalance in this case is 18%.
PRIMARY
SECONDARY (5A)
I
a
= 73 A
3.65 A
I
b
= 100 A
5 A
I
c
= 100 A
5 A
I
av
I
a
I
b
I
c
+
+
3
------------------------
73 100 100
+
+
3
--------------------------------------
A
273
3
---------
A
91 A
=
=
=
=
%UB
I
m
I
av
–
I
FLC
---------------------
100%
×
73 91
–
100
---------------------
100%
×
18%
=
=
=