Coil number
Description
Signal direction
1 - 16
Frequency converter control word (see table below)
Master to slave
17 - 32
Frequency converter speed or set-point reference
Range 0x0 - 0xFFFF (-200% ...
~
200%)
Master to slave
33 - 48
Frequency converter status word (see table below)
Slave to master
49 - 64
Open loop mode: Frequency converter output fre-
quency
Closed loop mode: Frequency converter feedback sig-
nal
Slave to master
65
Parameter write control (master to slave)
0 = Parameter changes are written to the RAM of the
frequency converter
1 = Parameter changes are written to the RAM and
EEPROM of the frequency converter
Master to slave
66 - 65536
Reserved
Coil
0
1
01
Preset reference LSB
02
Preset reference MSB
03
DC brake
No DC brake
04
Coast stop
No coast stop
05
Quick stop
No quick stop
06
Freeze outp
No freeze outp
07
Ramp stop
Start
08
No function
Reset
09
No jog
Jog
10
Ramp 1
Ramp 2
11
Data not valid
Data valid
12
Relay 1 off
Relay 1 on
13
Not used
Not used
14
Setup 1
Setup 2
15
Not used
Not used
16
No reversing
Reversing
Frequency converter control word (GE Drive profile)
Coil
0
1
33
Control not ready
Control ready
34
Unit not ready
Unit ready
35
Coasted
Not coasted
36
Error,
tripped
37
Error, no trip
38
Not used
Not used
39
Error, trip locked
40
No warning
Warning
41
Not on reference
On reference
42
Hand mode
Auto mode
43
Out of freq. range
In frequency range
44
Not running
Running
45
No res. brake fault
Resistor brake fault
46
No voltage warning
Voltage warning
47
Not in current limit
Current limit
48
No thermal warning
Thermal warning
Frequency converter status word (GE Drive profile)
Register number
Description
00001 – 00006
Reserved
00007
Last error code. See section
Exception and Error Codes
.
00008
Reserved
00009
Parameter index*
00100 – 00999
000 parameter group (parameters 001 through 099)
01000 – 01999
100 parameter group (parameters 100 through 199)
02000 – 02999
200 parameter group (parameters 200 through 299)
03000 – 03999
300 parameter group (parameters 300 through 399)
04000 – 04999
400 parameter group (parameters 400 through 499)
…
…
49000 – 49999
4900 parameter group (parameters 4900 through 4999)
50000
Input data: Frequency converter control word register (CTW).
50010
Input data: Bus reference register (REF).
…
…
50200
Output data: Frequency converter status word register (STW).
50210
Output data: Frequency converter main actual value register (MAV).
Table 5.2: Holding Registers
* Used to specify the index number to be used when accessing an indexed parameter
AF-60 LP™ Micro Drive Operating Instructions
30
DET-579A
5
Содержание AF-60 LP
Страница 1: ...AF 60 LPTM Micro Drive Operating Instructions GE Consumer Industrial Electrical Distribution ...
Страница 5: ...AF 60 LP Micro Drive Operating Instructions 4 DET 579A 1 ...
Страница 27: ...AF 60 LP Micro Drive Operating Instructions 26 DET 579A 5 ...
Страница 43: ...AF 60 LP Micro Drive Operating Instructions 42 DET 579A 6 ...
Страница 44: ...6 Parameter Overview AF 60 LP Micro Drive Operating Instructions DET 579A 43 6 ...
Страница 55: ...AF 60 LP Micro Drive Operating Instructions 54 DET 579A 7 ...
Страница 56: ...7 Troubleshooting AF 60 LP Micro Drive Operating Instructions DET 579A 55 7 ...
Страница 59: ...AF 60 LP Micro Drive Operating Instructions 58 DET 579A 8 ...
Страница 71: ...W Warnings And Alarms 55 56 AF 60 LP Micro Drive Operating Instructions 70 DET 579A ...