3.3 Motor Connection
3.3.1 How to Connect the Motor
See the chapter
Specifications
for correct dimensioning of motor cable cross-section and length.
•
Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both the decoupling plate and the motor
metal.
•
Keep motor cable as short as possible to reduce the noise level and leakage currents.
All types of three-phased asynchronous standard motors can be connected
to the frequency converter. Normally, small motors are star-connected
(230/400 V,
Δ
/Y). Large motors are delta-connected (400/690 V,
Δ
/Y). Refer to
motor nameplate for correct connection and voltage.
Illustration 3.3: Star and delta connections.
Step 1: First, mount the earth cable.
Step 2: Connect wires to terminals either in star or delta-connection. See mo-
tor nameplate for further information.
Illustration 3.4: Mounting of earth cable and motor wires.
AF-60 LP™ Micro Drive Operating Instructions
14
DET-579A
3
Содержание AF-60 LP
Страница 1: ...AF 60 LPTM Micro Drive Operating Instructions GE Consumer Industrial Electrical Distribution ...
Страница 5: ...AF 60 LP Micro Drive Operating Instructions 4 DET 579A 1 ...
Страница 27: ...AF 60 LP Micro Drive Operating Instructions 26 DET 579A 5 ...
Страница 43: ...AF 60 LP Micro Drive Operating Instructions 42 DET 579A 6 ...
Страница 44: ...6 Parameter Overview AF 60 LP Micro Drive Operating Instructions DET 579A 43 6 ...
Страница 55: ...AF 60 LP Micro Drive Operating Instructions 54 DET 579A 7 ...
Страница 56: ...7 Troubleshooting AF 60 LP Micro Drive Operating Instructions DET 579A 55 7 ...
Страница 59: ...AF 60 LP Micro Drive Operating Instructions 58 DET 579A 8 ...
Страница 71: ...W Warnings And Alarms 55 56 AF 60 LP Micro Drive Operating Instructions 70 DET 579A ...