- 10 -

Connect like above graph. Cut off the link between (4) and (6), the action loop take
39 turns, the brake circuit takes 14 turns, the regulator (minimum capacity 5KVA)
and the instrument uses the same 220V power supply, adjust the brake Current to
the required ampere turns, according to the AC relay to make the action current. If
the action ampoule is completely wrong, it is possible that the phase angle of the
braking current and the operating current is 180 ° and the braking current is
reversed. If the instrument uses a phase in the three-phase, the regulator uses the
other phase, and the phase angle of 60 ° can be obtained by changing the phase
difference and booster positive and negative connection. If externally connect phase
shifter, can get 0 ~ 360 ° phase angle.
2) The whole group of volt-ampere characteristics test, according to the following

diagram wiring:

Put AC current on winding (3), (8), read voltage by a multi-meter from (9), (10),
select 1 to the AC current gear, step up current to the required turns number, read
voltage value of the executive component terminal when turns is 1 times, 2 times, 5
times.
Ampere-turn test under setting position is the same as that of the current relay

Ⅵ、

Matters Need Attention

1. For safety reasons, do not turn on the power switch when the instrument and the
relay are connected. Check that the wiring is correct and then turn on the power
switch.
2. For the accuracy of the instrument, please preheat 5 to 10 minutes before the test.
3. When measuring the contact action time, the millisecond meter should be cleared
after adding the rating.
4. When the instrument is not working properly, please check the various insurance

Содержание ZXJB

Страница 1: ...ZXJB Single Phase Relay Protection Tester ...

Страница 2: ...ts Ⅰ Product Introduction 2 Ⅱ Technique index 2 Ⅲ Panel layout diagram and function 3 Ⅳ Output power supply operation 4 Ⅴ Instructions 5 Ⅵ Matters Need Attention 10 Ⅶ Packing list 11 Ⅷ Maintenance and Repair 11 ...

Страница 3: ...eration and ideal for Power Industry relay protection department Ⅱ Technique index 1 Working condition 1 Working power supply AC220V 10 50Hz 2 Working environment temperature 10 40 humidity 85 3 Atmosphere Pressure 86 106Kpa 2 Output power supply 1 AC voltage 0 250V 3A 2 AC current 0 100A 7 5V 0 20A 25V 0 5A 5V 3 DC voltage 0 220V 3A 4 DC current 0 20A 25V 5 Setting output DC24V DC48V DC110V DC220...

Страница 4: ...test 6 Other unconventional relays and LV circuit breakers Ⅲ Panel layout diagram and function Panel layout diagram 1 Function description 1 J1 J2 J3 J4 J5 are respectively AC DC power source and setting value output terminal as it shows in the panel 2 X1 indicates current voltage value display starting value return value and rated value X2 is Millisecond Meter 3 S1 is power supply socket S2 is po...

Страница 5: ...connect with normally open contact the indicating lamp will be turned on after operation and if connect with normally closed contact the indicating light will be off after operation 8 Synchronization control the on off of the output voltage current to make short t e s t o n r e l a y r a t e d v a l u e 9 Set setting value output switch 10 Reset clear operation for Millisecond meter 11 Reclosing c...

Страница 6: ...e instrument 5 Setting value output 1 Turn T2 to 24V close set switch J5 terminal output constant DC voltage 24V 2 Turn T2 to 48V close set switch J5 terminal output constant DC voltage 48V 3 Turn T2 to 110V close set switch J5 terminal output constant DC voltage 110V 4 Turn T2 to 220V close set switch J5 terminal output constant DC voltage 220V Ⅴ Instructions 1 Measurement Can work as independent...

Страница 7: ... return value Return value divided by operation value then multiply by 100 to get return factor Relay time measurement Regulate output power according to point 4 turn T3 to relay contact state push synchronous switch rotate slowly T4 Knob to relay rated value Relay time can be tested via synchronous switch display value of 2 Note that the Millisecond meter should be zero cleared and reclosing swit...

Страница 8: ...J3 to 1 to separate ZJ3 contact Turn T1 to DC20A switch on power and turn T4 to relay rated current value then switch off power turn T2 to relay rated voltage value Turn T3 to I position that s relay ZJ3 contact state Switch on power push setting value button reset millisecond after charging for 15 25 seconds the charging time can be read from millisecond meter Push reclosing button to measure rec...

Страница 9: ... same as rated current value then cut off voltage regulate protection coil current T4 the minimum hold current of the relay is the minimum hold value Operation time and return time test refer to point5 2 Differential relay BCH 1type as example Item 4 9 10 test can be done without external device Item 6 test can be done when match with external voltage regulator and current generator Others not wit...

Страница 10: ...sed to test the voltage between the two ends of J1 No brake Starting ampere turns test It is not normal inspection item Put in all the working winding 20 circuits connect the short circuit of 10 and 11 input AC current from 3 and 8 input contact operation signal from 5 7 contact end test like that for current relay The braking performance test When make periodic inspection just test Φ 0 and Action...

Страница 11: ...hase shifter can get 0 360 phase angle 2 The whole group of volt ampere characteristics test according to the following diagram wiring Put AC current on winding 3 8 read voltage by a multi meter from 9 10 select 1 to the AC current gear step up current to the required turns number read voltage value of the executive component terminal when turns is 1 times 2 times 5 times Ampere turn test under se...

Страница 12: ...se turn off the instrument before removing the wiring 7 Before using the instrument please read the instruction manual carefully Ⅶ Packing list 1 The main machine 1pcs 2 Power line 1thread 3 Testing line 1set 4 Fuse 6 4A 4pcs respectively 5 Manual 1 copy 6 Inspection Report 1copy 7 warranty card 1copy Ⅷ Maintenance and Repair Products should be placed in a ventilated cool dry clean place for prese...

Отзывы: