Revision 1.1
GM ECx Instruction Manual
23
6.9
LCD Contrast Adjustment:
LCD Contrast Adj.
may be set for optimum viewing using the menu shown in Figure 6-10.
CONTRAST
UP/DOWN to change
NEXT to EXIT
Figure 6-10: LCD Contrast Adjust Menu
SECTION 7 – TECHNICIANS ONLY MENUS
7.1 Introduction:
WARNING
! Users of these menus must have a detailed understanding of their functions.
Monitoring of target gases, processing of alarms, Modbus wireless communications should not be
relied upon while editing these menus! Back-up the current configuration prior to altering any
Technical menus in case Restore is required later (see section 6.3).
The
TECHNICIAN
ONLY
menu group in Figure 7-1 contains items that are
factory configured
depending upon the type sensor and input connected to the GM ECX. They should not be
tampered with after installation. If configured incorrectly, some items will prevent monitoring of
target gases.
The Set Sensor Voltage
menu for setting the catalytic bead sensor excitation
voltage could destroy the sensor.
Access requires a special key sequence of four
consecutive UP keystrokes
to prevent accidental modification of critical items.
Figure 7-1: Technicians Menu Tree