GDS 450L Скачать руководство пользователя страница 9

 

9

 
Connections to Control Board 

 
Supply 

Connect a 

10A 240v non earth leakage

 protected power supply to Din Rail terminals labelled A & N 

Connect earth to the earth Din Rail terminal. 

The VSD unit inherently operates with a small amount of earth leakage current which may cause nuisance 
tripping of an earth leakage circuit breaker. 

 

Motor Wires 

Connect the shielded motor cable to Inverter terminals. Connect earth and shield to Earth Stud. 

 

Control 

Connect low voltage limit switch wires to limit switch terminals on circuit board.  Note the common terminal and 
open/close terminals for motor one and motor two.  Connect the shield (if used) to earth. 
 

Control Inputs 

The P.E, OPN and STP inputs require a normally closed switch contact and therefore should be shorted to the COM 
terminal if not used.  This is done via bridging links already on the circuit board (bottom left corner) The CLS, OSC 
and PED inputs require a normally open switch contact and therefore should be left unconnected if not used. All the 
switch inputs of this control board including the limit switch inputs require a voltage free switch contact only. Do not 
connect any switches which provide a voltage to the control board as this will damage the control board. If the inputs 
are 12/24v or has long wiring associated with it use an IM-1 module to isolate it from the control board’s input. The 
IM-1 is available from the manufacturer. 

 

Powering Accessories 

Accessories which require a 24v AC supply can be powered from the transformer output used to power the control 
board via the isolated 24v AC supply which is connected to the DIN rail terminals as labelled.  However the 
transformer’s current capacity must be checked to allow for the extra power required by the accessories. Never use the 
supply connected to the 24v AC supply control board terminals to power any accessory as this can interfere with the 
control boards operation. (Blue Wires) 

 
Locks & Lights 

Use the lock output terminals on the din rail to switch the 12 volts to an electric lock (if fitted). The load switched by 
the lock output terminals must not exceed 30v AC / DC @ 5Amps.  If a electro magnetic lock is used, change one 
wire on the control board lock output to the normally closed output.  Use the light relay module (if fitted) to switch the 
applied voltage to a light. The load switched by the light relay module must not exceed 240v AC / 30v DC @ 10 
Amps.  
 

Setting Cycle Timers & Auto Close Times

 

The control board has pre-set cycle times which are used to set the maximum time the controller will drive the motors 
in the open and closed directions. The pre-programmed time for the open and close cycle timer’s is 60 seconds. The 
control board also has a pre-set pedestrian access time of 5 seconds which is intended to open the motor connected to 
M1 output only part way. If these default times do not suit your needs simply use the procedure below to adjust them. 
Note the same procedure can be used to adjust the auto-close times. 

1.

 

Place the slide switch into the “set” position  

2.

 

Adjust the timer’s value by pressing and holding the required push button for the desired time. 

3.

 

Repeat step 2 for the next timer (if desired). 

4.

 

Place the slide switch back into the “RUN” position. 

5.

 

Test operation.  

Make sure that the slide switch is placed back into the “RUN” position before testing the new timer value.  
As you can see the procedure used to set each timer’s value is the same only the push button used changes. Each push 
button is clearly labelled underneath as to which timer’s value it sets. Note when setting the OPEN, CLOSE and 
PEDESTRIAN cycle times the controller will drive the motors as if a “real” cycle is being executed. The difference 
being that the motors will stop as soon as the button is released or the limit switches are reached. The OPN status LED 
on the control board will flash at 1 second intervals to assist setting times. Note when setting the OPEN and CLOSE 
cycle times when limit switches are used, release the push button a few seconds after the limit switch cuts motor 
power. This allows for the motors to slow down over the life of the operators without the need to adjust again. 

 

Содержание 450L

Страница 1: ...ity imported components Installation and Maintenance Manual Sliding Gate Operators Models GDS 450L 630L Range Made in Australia from Australian quality imported components A B N July N14870 Installation and Maintenance Manual Sliding Gate Operators Made in Australia from Australian quality imported components ...

Страница 2: ...n the rack teeth and Pinion wheel Once the rack is fixed move the gate and sight the rack moving over the pinion wheel check that most of the pinion wheel meshes with the rack Make sure rack runs freely over the pinion wheel any tights spots should be corrected by adjusting the rack height Check the operator is firmly bolted down to the concrete pad Ensure stops are installed on the gate for the f...

Страница 3: ...the gate travels is in accordance with the opening and closing status LED s if not reverse two of the motor wires at the inverter terminals Inverter settings can be adjusted via the keypad i e Opening speed closing speed and ramp times Automation settings operating modes are able to be adjusted via the CB6 board refer to manual for further instructions Once Inverter settings are appropriately set ...

Страница 4: ... Precautions 5 2 Wiring Requirements 6 3 Installation Details 6 10 Electrical cabling Mechanical installation Electrical connections Operator dimensions CB 6 control board layout Inputs Outputs Mode descriptions 4 Variable Speed Drive VSD 10 5 Commissioning 11 6 Control Diagrams 12 ...

Страница 5: ...gateposts or mounting structure has the necessary strength and rigidity to support the operator and the load of the opening and closing gate motion Always incorporate the appropriate Photo Electric Cells Induction Loops and any other safety devices to protect both equipment and personnel Extra caution should be employed when using operator in auto Display any necessary signs to indicate any danger...

Страница 6: ...osed positions These stops need to be engineered and installed such that they will be strong enough to stop the gate should the limits fail at any time Remove the gate operator cover and position mounting plate and operator in approximate mounting location Use the rack to locate the operator the correct distance away from the gate rail finer adjustment can be made after Dynabolt or chemical anchor...

Страница 7: ...7 Operator Dimensions ...

Страница 8: ...iver 7 Motor 2 Limit Switch Inputs no t shown 8 Terminals for Isolated 24vAC Supply 21 Firmware Version Label for Limit Switch and Control Inputs 22 Light Control Relay Interface 9 Pedestrian Access Control Input Connector 10 Open Stop Close Control Input 23 Input Status L E Ds 11 Close Control Input 24 Stop Input Jumper 12 Stop Control Input 25 Open Input Jumper 13 Open Control Input 26 PE Beam I...

Страница 9: ... din rail to switch the 12 volts to an electric lock if fitted The load switched by the lock output terminals must not exceed 30v AC DC 5Amps If a electro magnetic lock is used change one wire on the control board lock output to the normally closed output Use the light relay module if fitted to switch the applied voltage to a light The load switched by the light relay module must not exceed 240v A...

Страница 10: ...ut also resets the P E triggered auto close mode so that the P E input will need to be triggered again before a P E auto close cycle will be initiated Position 5 M 2 OUTPUTS STATUS OFF The M2 output controls second motor ON The M2 output controls status lights Position 6 P E STOPS CLOSE CYCLE OFF Activating the P E input while motors are closing causes the motors to reverse ON Activating the P E i...

Страница 11: ...ator led s go out when the corresponding limit switch is activated If they are the wrong way around swap over the M1 op and cl limit wires They can be roughly set so they activate approx 500 to 800mm before the gate reaches its end stops Final adjustments can be made later Position the gate halfway and turn the knurled knob clockwise until the clutch is firm enough that the gate will drive but the...

Страница 12: ......

Страница 13: ...opened by hand To re engage the clutch move the gate by hand Into approx The half way position and turn the Knurled knob clockwise until it is very tight If when turning the knurled knob clockwise and It just spins either try spinning it clockwise with more force to release it off of the hexagonal retaining nut or hold the nut with one hand and turn the knurled knob clockwise ...

Страница 14: ...G Failure to maintain equipment may result in injury or death and or damage to property and equipment Recommended maintenance to be performed on the operator and gate are as follows Operator performs over 150 cycles a day each month Operator performs between 100 150 cycles a day every 2 month 99 cycles a day every 4 months 49 cycles a day every 6 months Operator performs under 20 cycles a day ever...

Страница 15: ...circumstances i If no proof of date of purchase can be produced ii If the product has been used in a manner beyond its design parameters iii If the product is tampered with or repaired by personnel not authorised to do so iv In respect of loss or damage caused by rough treatment v If the product is not used and maintained in accordance with instructions or recommendations listed in this Installati...

Отзывы: