Technical

Gas Type

 

Oxygen

Input Voltage

 

12~30v DC – 24v nominal
Optional Mains 230/115vAC 50/60hz
Nominal 30mA – 120mA full alarm

Output Standard

 

Analogue 4~20 mA (250 ohms max) – sink/source
(source mode – standard)
Option 1~5v output – solder G

CV–Sensor Cable

 

3 core screened

Alarm Relay 

 

Main relay S.P.C.O. 3A/230v AC
Fire Alarm panel signalling – cut F
Trip Indicator LED – trip point selectable 10% to full scale  

(Auto reset)
On board sounder
Auxiliary output DC volts – standard–as input volts 24v
DPM – gas readout display – (zero and span potentiometers used 

only for DPM setting)

www.gds–technologies.co.uk

SET UP PROCEDURE

Installation 

Siting of the equipment should be chosen with regard to the 

following points: 
1.  Safe area use only (not hazardous zone)
2.  Away from sources of heat and with room for adequate air 

circulation. 

3.  Within easy reach for operating and maintenance personnel. 
4.  Connecting cables to be electrically shielded.
5.  For further information regarding sensor location see our website  

www.gds–technologies.co.uk.

Note: Sensor cables should not be run in the same ducting as power 

cables.

Removing Lid (30J)

Using a 2.5mm Allan key withdraw the two lid screws until they clear 

the lid bezels. Push the lid up until it is stopped by the circuit board 

located inside the enclosure; pull one side to remove the lid.

Mounting

Direct wall mount – use M4 or No.8 screws through the membrane 

of the 4 stand–offs. Where the stand–offs are to be removed (rotate 

each stand–off using pliers) drill at mounting points marked C or 

utilise knock out slots.

For surface mount box drill at points B (2 off)
For conduit box fixing drill at points A (2 off)

Supply Input

Ensure that the supply is correct for the voltage rating of the 

indicator. Ensure that the supply is OFF before making any 

connections and wire only in accordance with the terminal detail.

Calibration (factory set)

1.  Connect a digital voltmeter (miIIivolt range) to the X and Y test 

terminals, the CV is preset in the current source mode.

2.  Remove the sensor terminal connector from the PCB J4 or yellow 

wire and adjust the 4mA potentiometer for 4mA (4mV).

3.  Where a digital panel meter is fitted to the CV card the reading 

may be adjusted by the DPM Zero potentiometer.

Reconnect the cell and allow reading to stabilise adjust the DVM 

reading to 17.3mV (20.8% ambient oxygen) using the 20mA 

potentiometer.

Where a Digital panel meter is fitted the display may be adjusted by 

using the DPM S potentiometer (span).

Alarm Trip Point Adjustment (factory set)

This level will normally be set at 23% for oxygen.
1.  Connect the DVM as above, using the 20mA potentiometer adjust 

for the required trip level (OM DPM).

2.  Adjust the alarm level potentiometer until the alarm LED just 

comes on.

3.  Using the 20mA potentiometer re–adjust the DVM to 17.3mV.
The above adjustment may be carried out in house by connecting 

the CV transmitter directly to a DC power supply and connecting a 

100Ω load resistor. See diagrams on left.

Should a full board be required to operate on a 2 wire 4-20mA loop 

then the alarm relay / LED must be disabled – remove JP2.

A

B

C

D

X

P

-

-

+

-

+

+

Y W

P Y W

SENSOR

FIELD TERMINALS

TO GDS

ALARM PANEL

PCN149

E

Y

20mA

4mA

TP2 TP4

TP1

RV3

JP1

RV4

TP3

W Y P

No C Nc

NC
C
NO

- +

Sensor Terminal

Sounder Mute

Sounder

FULL CV BOARD

T

RELAY

BOARD

CV

TRANSMITTER

EOL

Output Signal

Adjust

Test Points

Alarm Level

Adjust

Alarm

LED

JP2

20mA

4m

A

Span

Zero

DP

M

E

A

JP1

-

+

W Y R

- +

J4

JP3

JP4

X

Y

B

C

D

W+

SIG

P -

Field Terminals

to GDS Alarm Unit

U5

LK1

A L

SAFE AREA BOARD

EExd BOARD

-

+

-

+

E

SIG

-

+

-

+

E

SIG

JP1 Jumpers BD

JP1 Jumpers AC

3 Wire Sink

100Ω load

100Ω load

3 Wire Source

2 Wire 

24vDC 

24v DC

Output

W Y P

No C Nc

NC
C
NO

-

+

+

Sensor

Terminal

Sounder

RELAY

BOARD

Sensor

Terminal

EOL

Output Signal

Adjust

Test Points

Alarm Level

Adjust

Alarm

LED

JP2

20m

A

4m

A

Span

Zero

DP

M

E

A

JP1

-

+

W Y R

- +

J4

JP3

JP4

X

Y

B

C

D

W+

SIG

P -

Field Terminals

to GDS Alarm Unit

U5

LK1

A L

T

1A

Relay

RL2

3A

Relay

RL1

-

24v DC

Output

+

-

Содержание 10+ OXYMED

Страница 1: ...in the vicinity of assisted breathing apparatus requiring oxygen cylinders or dedicated oxygen supply lines The compact style offers functionality for the monitor to be used as a fixed or a transportable device boasting further benefits for quick installation via a standard wall socket outlet GDS 10 OXYMED OXYGEN MONITOR ...

Страница 2: ...he indicator Ensure that the supply is OFF before making any connections and wire only in accordance with the terminal detail Calibration factory set 1 Connect a digital voltmeter miIIivolt range to the X and Y test terminals the CV is preset in the current source mode 2 Remove the sensor terminal connector from the PCB J4 or yellow wire and adjust the 4mA potentiometer for 4mA 4mV 3 Where a digit...

Страница 3: ...r bedding within the area If you suspect contamination remove items outside for airing 3 Siting the Equipment Siting of the equipment should be chosen with regards to the following points Away from sources of heat with room for adequate air circulation Convenient to a 230v mains socket outlet Within easy access and audible distance of local staff Within the target area at 1 to 1 5m height 4 Operat...

Страница 4: ...147 W 145 D 100mm AC Version Weight 0 76KG AC Version Enclosure Material ABS Flame Retardant FR40 Lid Screws M4SS Finish Signal White RAL 9003 Notes Mains lead supplied as standard For additional information please see C1798 SPECIFICATION GDS Technologies Ltd operates under an integrated quality health and safety and environmental management system certified to ISO 9001 ISO 45001 and ISO 14001 by ...

Отзывы: