GASMAX CX + GDS-IR Operation & Maintenance Manual, Revision 1.0
Page 21
7
TROUBLESHOOTING
GASMAX
CX
SHOWS
FAULT
INDICATION
ON
LOCAL
SENSOR
Certain.
Toxic
sensors
Sensor
reading
Sensor
GASMAX
CX
SHOWS
FAULT
INDICATION
ON
REMOTE
SENSOR
Catalytic
Sensor
reading
Sensor
re
RECEIVING
DEVICE
AND
GASMAX
CX
DISPLAYED
VALUES
DON’T
MATCH
Check
that
zero
and
full
scale
range
values
match
between
GASMAX
CX
and
receiving
device
(controller).
Use
DIAGNOSTICS
menu
to
force
GASMAX
CX
output
to
12mA
(1/2
scale)
and
verify
appropriate
half
‐
scale
reading
on
controller.
Check
for
high
impedance
shorts
to
ground
on
4
‐
20mA
wiring.
If
4
‐
20mA
output
is
off
‐
scale
low
or
high
and
cannot
be
adjusted
using
DIAGNOSTICS
mode,
IO/Power
Supply
board
may
be
defective
and
should
be
replaced.
CONTROLLER
MODBUS
DATA
INCORRECT
Verify
the
MODBUS
master
is
requesting
data
from
registers
31001
for
CH
1,
31002
for
CH
2.
Verify
that
controller
MIN
and
MAX
count
settings
are
correct.
MIN
counts
should
be
“800”
which
corresponds
to
4mA
and
MAX
counts
should
be
“4000”
which
corresponds
to
20
mA.
Verify
that
the
GASMAX
MODBUS
address
matches
the
address
programmed
into
the
controller’s
channel
configuration.
CONTROLLER
SHOWING
MODBUS
COMM
ERROR
Check
for
incorrect
MODBUS
polarity
(swap
“A”
and
“B”
if
unsure;
no
damage
will
occur).
Verify
that
MODBUS
master
is
requesting
data
from
correct
MODBUS
address.
Verify
that
MODBUS
master
is
requesting
correct
registers:
31001
for
CH
1,
31002
for
CH
2.
Verify
that
there
are
no
other
MODBUS
slave
devices
with
identical
MODBUS
address.
GASMAX
CX
DISPLAY
BLANK
Verify
DC
power
at
IO/Power
Supply
board,
TB1,
terminals
1
(+24)
and
4
(Gnd).
Verify
ribbon
cable
connected
between
IO/Power
Supply
board
and
Display
Assembly.
SOFTWARE
RESET
(“COLD
BOOT”)
If
the
GASMAX
CX
display
shows
‘nonsense’
characters
or
one
or
more
of
the
settings
appear
to
be
corrupted,
performing
a
“Cold
Boot”
will
restore
the
default
values
in
the
non
‐
volatile
memory
and
may
clear
the
problem.
To
perform
a
‘Cold
Boot”,
hold
the
magnetic
wand
over
the
EDIT
key
while
applying
power.