8.3 MAINTENANCE WORK
8.3.1 Cleaning
NOTE!
•
All cleaning agents must be compatible with the materials of the installed component.
8.3.2 Requirements for maintenance
Check before maintenance start, if:
•
no gas supply is connected to the panel
•
gas supply panel is depressurized
•
no process gas is inside the gas supply panel
•
gas supply panel is purged and filled with Nitrogen
8.3.3 Necessary maintenance
•
Check accuracy of pressure gauges
•
Panel and gauges: check condition, function and labelling
•
Check labelling
•
Check for corrosion
•
Check function
•
Pressure test with 1-times working pressure for 12 hours
•
Worn and defective components have to be changed immediately from authorized qualified company
•
If there are any leakages or too much corrosion at the panel, it has to be replaced with all connections by
an authorized company.
•
After the changing of components or tubes, pressure and leakage test have to be done again and be
protocolled
8.4 MEASURES FOLLOWING MAINTENANCE
The following steps must be performed when the maintenance works have been completed and before
switching on the system.
1. Make sure that all tools, materials and other equipment have been removed from work area.
2. Clean the work area and remove any spilled substances, e.g. liquids, processing material or similar.
3. Make sure that safety relevant components are working perfect.
TROUBLESHOOTING
The following section describes possible causes of malfunctions and how to eliminate them.
If malfunctions occur with increasing regularity, shorten the maintenance intervals to reflect the actual load.
If malfunctions occur that cannot be eliminated with the following help, please contact the manufacturer (see
section 1.8 for contact details).
9.1 SAFETY NOTES FOR TROUBLESHOOTING
In any case of malfunction the shut-off valves of the connected gas containers have to be closed. Never oper-
ate devices with malfunction under pressure.
What to do in case of malfunction:
1. Interrupt gas supply
2. Depressurize panel with handwheel
3. Only trained technical staff may eliminate malfunctions.
4. Restore the gas supply panel to its original state.