GCAN GC-4642 Скачать руководство пользователя страница 8

Vhandy Technology

GC-4642 user manual

3. Technical specifications

Interface characteristics

Output points

2

Signal voltage

0mA~20mA

load

5k

Ω

(Short circuit protection)

power supply

Powered by external 24V

Resolution

16 bits

Conversion time

4ms

Measurement error

<±

0.1% (full scale)

ESD rating

7 kV

Electrical isolation

2500 Vrms

Current consumption

150mA

Bit width in process image

Output: 2 x2 bytes

configuration

No address setting, configuration via bus

coupler or controller

Pluggable wiring

Suitable for all GCAN-PLC-400 series,

GCAN-8000 series bus terminal modules

Environmental test

Operating temperature

-40

~+85

Working humidity

95%RH, no condensation

EMC test

EN 55024:2011-09

EN 55022:2011-12

Anti-vibration/impact

resistance

EN 60068-2-6/EN 60068-2-27/29

Anti-electromagnetic

interference/anti-electromagn

etic radiation performance

EN 61000-6-2 /EN 61000-6-4

Protection class

IP 20

Basic Information

Dimensions

100mm *69mm *12mm

weight

50g

Содержание GC-4642

Страница 1: ...GC 4642 2 channel analog output module 0mA 20mA User manual Document version V3 01 2020 12 21...

Страница 2: ...s 4 1 2 Typical applications 4 2 Equipment installation and use 5 2 1 Module fixing 5 2 2 Wiringmethod 5 2 3 System status indicator 7 2 4 Use in combination with PLC400 510 series 7 2 5 Combination w...

Страница 3: ...The signal voltage is 0mA 20mA Powered by external 24V The load is greater than 5k short circuit protection Measurement error is less than 0 1 full scale The measurement resolution is 16 bits Convers...

Страница 4: ...ttach the GC 4642 module to the right of the fieldbus coupler or other modules to add this component As shown in Figure 2 1 insert the GC 4642 module inwards along the slot until the latch snaps The G...

Страница 5: ...le installation Figure 2 3 GC 4642 module terminal block The terminal block of GC 4642 module is shown in Figure 2 3 GC 4642 contains 2 sets of output points and can connect up to 2 sets of analog sig...

Страница 6: ...signal activation not bright Output signal is not activated Table 2 3 GC 4642 module indicator status 2 4 Use in combination with PLC400 510 series GCAN PLC 400 510 supports programming in five langua...

Страница 7: ...of the output module then no matter how many input modules are in front the address of the first output module is still Q0 0 2 5 Combination with GCAN IO 8000 series equipment The status of the analo...

Страница 8: ...image Output 2 x2 bytes configuration No address setting configuration via bus coupler or controller Pluggable wiring Suitable for all GCAN PLC 400 series GCAN 8000 series bus terminal modules Environ...

Страница 9: ...efully Once used it is deemed to be an endorsement and acceptance of the entire content of this statement Please strictly abide by the manual product description and related laws regulations policies...

Страница 10: ...CAN Digital input GC 1008 Digital input PNP 24V DC 8 channel GC 1018 Digital input NPN 24V DC 8 channel GC 1502 Counter 200kHz max 2 channel Digital output GC 2008 Digital output PNP 24V DC 8 channel...

Страница 11: ...6 bits 10V 10V 2 channel GC 4642 Current output 16 bits 0 20mA 2 channel GC 4652 Current output 16 bits 4 20mA 2 channel GC 4662 Voltage output 16 bits 0 5V 2 channel GC 4672 Voltage output 16 bits 0...

Страница 12: ...manual Sales and service Shenyang Vhandy Technology Co Ltd Address No 135 21 Changqing Street Hunnan Shenyang Liaoning China E mail sygckj gmail com Tel Whatsapp 86 13644001762 Skype live sygckj WeCh...

Отзывы: