SFAR-1M-4DI User Manual
Version 3.0
www.gc5.pl
Page 12 / 13
6.2.
Bit access
Modbus
Address
Dec
Address
Hex
Address
Register name
Access
Description
193
192
0x0C0
Default state of output
1
Read & Write
Default state of output 1
194
193
0x0C1
Default state of output
2
Read & Write
Default state of output 2
10801
800
0x320
Input 1
Read
Input 1 state
10802
801
0x321
Input 2
Read
Input 2 state
817
816
0x330
Output 1
Read & Write
Output 1 state
818
817
0x331
Output 2
Read & Write
Output 2 state
1153
1152
0x480
Capture 1
Read & Write
Capture counter 1
1154
1153
0x481
Capture 2
Read & Write
Capture counter 2
1169
1168
0x490
Captured 1
Read & Write Captured value of counter 1
1170
1169
0x491
Captured 2
Read & Write Captured value of counter 2
Table 7 - Bit access