3.3. Electrical Specifications (Standard Type)
ITEMS
SPECIFICATION
Input Voltage(Standard)
※ Customer supplied PSU must meet
requirements IEC1010-1 and CE
Marking requirements.
Absolute min:
Nominal:
Absolute max:
Ripple maximum allowed:
18V
24V
31V
1V pk-pk
Wattage
Max. wattage:
Max. current:
4.8W @+24 VDC
200mA @+24 VDC
Analog output Current
0-20mA(500 ohms max load)
All readings ± 0.2mA
Measured-value signal:
4mA(Zero) to 20mA(Full Scale)
Fault:
0-100% LEL:
100-109%LEL:
Over 110% LEL:
Maintenance:
0mA
4mA - 20mA
20mA - 21.4mA
22mA
3mA
Analog output current ripple & noise max
±20uA
Relay contact
Alarm1, Alarm2, Fault Relay
Rated 1.0 A @ 30VDC or 0.5 A @ 125 VAC
Wiring requirement
Power
CVVS or CVVSB with shield
Analog
CVVS or CVVSB with shield
RS485
STP(Shielded Twisted Pair)
Cable Connection Length
Analog
2500m
RS485
1000m
EMC Protection:
Complies with EN50270
3.4. Environmental Specifications
ITEMS
SPECIFICATION
Operation Temperature
Transmitter
-20 to 60 ℃
Sensor
Refer to Sensor Specification
Storage Temperature
Transmitter
-20 to 60 ℃
Sensor
Refer to Sensor Specification
Operation Humidity
Transmitter
5 to 99% RH (Non-condensing)
Sensor
Refer to Sensor Specification
Pressure Range
90 to 110KPa
Max. air velocity
6m/s
3. Specification
GTD-3000Ex
Instruction Manual