GTC-540
Instruction Manual
- ON/OFF of Energizer Mode is determined by "UP" S/W or "DOWN" S/W.
- When ON, it is in Normal Open (NO) status.
- When OFF, it is in Normal Close (NC) status.
- When a desired energizer mode is displayed, press "FUNC" S/W to set it and enter the next item.
- When "RESET" S/W is pressed, it returns to Alarm Setting Mode.
- Mode that sets external warning lights to operate with a desired alarm.
- When "FUNC" S/W is pressed, it enters Alarm Lamp setting mode.
- When "RESET" S/W is pressed, it returns to Alarm Setting Mode.
- Select a desired Alarm using "UP" S/W and "DOWN" S/W then set using "FUNC" S/W.
- By default, it is set at "OFF".
- When Alarm goes off when Alarm Lamp is ON, warning light is on. When it is OFF, warning
-
light is off.
- When a desired ALP value is displayed, press "FUNC" S/W to set it and enter the next item.
- When "RESET" S/W is pressed, it returns to Alarm Setting Mode.
- Alarm 1 threshold setting function message is displayed as "AL-1"
- Press "FUNC" S/W to enter Alarm 1 threshold setting function.
- When "RESET" S/W is pressed, it returns to Alarm Setting Mode.
- Function to change Alarm 1 threshold setting. Max. allowable is high scale value. Pressing "UP"
-
S/W or "DOWN" S/W increases or decreases Alarm1 value, respectively.
- When a desired alarm 1 threshold is displayed, press "FUNC" S/W to set it and enter the next item.
- When "RESET" S/W is pressed, it returns to Alarm Setting Mode.
- (Default: Alarm1 = 20(F/S 20%), Alarm2 = 40(F/S 40%), Alarm3 = 50(F/S 50%))
- Alarm level is set to the concentration outlined in domestic regulations as factory setting.
- It is a mode to set a direction of Alarm 1 operation. Pressing "UP" S/W or "DOWN" S/W displays
-
"H" or "L", respectively.
- "H" mode operates when gas value is equal or greater than Alarm1 setting value. "L" mode
-
operates when gas value is equal or less than Alarm1 set value.
- When a desired mode is displayed, press "FUNC" S/W to set it and enter the next item.
- When "RESET" S/W is pressed, it returns to Alarm Setting Mode.
- It is a mode to set a dead band for Alarm 1 operation. Pressing "UP" S/W or "DOWN" S/W
-
increases or decrease the value, respectively. (Default 0)
- When Alarm 1 is in "H" mode, Alarm 1 operates at values above the sum of Alarm and dead
-
band values and releases below the sum.
- When Alarm 1 is in "L" mode, Alarm 1 operation below difference of Alarm and dead band
-
values and releases above the difference
- When a desired Alarm1 dead band value is displayed, press "FUNC" S/W to set it and enter the
-
next item.
- When "RESET" S/W is pressed, it returns to Alarm Setting Mode.
- It is a mode to set Alarm1 delay time.
- It is a function to prevent instantaneous malfunction of detector due to external shock and noise
-
other than from normal operation.
- Press "FUNC" S/W to enter Alarm 1 dwell time setting function.
- When "RESET" S/W is pressed, it returns to Alarm Setting Mode.
▼ ▲
Full Range
▼ ▲
▼ ▲
6. Operation Method
6. Operation Method