Specifications
9.1
Fire Detection
•
Detection time and distance:
•
F-Guard-UV-IR:
o
5ms
-
for fast fire burst or explosion
o
1s
-
for 1ft
2
(0.1m
2
) N-heptane pan fire at 0-50 ft (0-15m)
o
<2s
-
for 1ft
2
(0.1m
2
) N-heptane pan fire at 50-100 ft (15-30m)
•
F-Guard-UV-IR-F
o
5ms
-
for fast fire burst or explosion
o
1.5s
-
for 1ft
2
(0.1m
2
) N-heptane pan fire at 0-50 ft (0-15m)
o
<3s
-
for 1ft
2
(0.1m
2
) N-heptane pan fire at 50-100 ft (15-30m)
•
Field of view: 90° Horizontal, 80° Vertical
•
Time Delay: 0-30 seconds (adjustable)
•
Built-in test: Automatic and Manual
9.2
Electrical Specifications
•
Operating Voltage: 24 VDC nominal (18-32 VDC)
•
Current Consumption:
o
Standby
120mA
o
Maximum
180mA all systems in operation (including window heater)
•
Cable Entries: 2x conduit entries 3/4” 14NPT or M25x1.5; with one entry plugged with a certified
stopper.
•
Wiring: 14-17AWG (2.5-1.0mm
2
)