Operating Principle of the Unit

DC Inverter Air to Water Heat Pump is composed of outdoor unit, indoor unit and internal-fan coil water tank.

Operation functions:

Cooling;

(1) Heating;
(2) Water heating;
(3) Cwater heating;
(4)  water heating;
(5) Emergency mode;
(6) Quick water heating;
(7) Holiday mode;
(8) Forced Operation Mode;
(9) Silent mode;
(10) Disinfection mode;
(11) Weather-dependent Operation;
(12) Floor debugging;
(13) Air removal of the water system;
(14) Other thermal

Cooling

:

in cooling mode, the refrigerant is condensed in the outdoor unit and evaporated in the indoor unit. Via the heat exchange

with water in the indoor unit, the temperature of water decreases and it releases heat while the refrigerant absorbs heat and
evaporates. With the help of wired controller, the outflow temperature can meet the user’s requirement. Through the control of valve,
the low-temperature water in the system is connected with indoor fan coil and underground pipe, and exchanges heat with the indoor
air so that the indoor temperature decreases to the required range.

Heating

:

in heating mode, the refrigerant evaporates in the outdoor unit and is condensed in the indoor unit. Via the heat

exchange with water in the indoor unit, the water absorbs heat and its temperature increases while the refrigerant releases heat and is
condensed. With the help of wired controller, the outflow temperature can meet the user’s requirement. Through the control of valve,
the high-temperature water in the system is connected with indoor fan coil and underground pipe, and exchanges heat with the indoor
air so that the indoor temperature increases to the required range.

Water

heating

:

in water heating mode: the refrigerant evaporates in the outdoor unit and is condensed in the indoor unit. Via

the heat exchange with water in the indoor unit, the water absorbs heat and its temperature increase while the refrigerant releases
heat and is condensed. With the help of wired controller, the outflow temperature can meet the user’s requirement. Through the
control of valve, the high-temperature water in the system is connected with the coil pipe of bearing water tank, and exchanges heat
with the water in the water tank so that the temperature of water tank increases to the required range.

Cooling

+ water

heating

:

when cooling mode exists together with the water heating mode, the user can set the priority of these two

modes based on the needs. The default priority is heat pump. That is under the default setting, if cooling mode exists together with
the water heating mode, the heat pump gives priority to cooling. In that case, water heating can only realized with e-heater of the
water tank. Inversely, the heat pump gives priority to water heating and switches to cooling after finishing water heating.

water

heating

:

when heating mode exists together with the water heating mode, the user can set the priority of these two

modes based on the needs. The default priority is heat pump. That is under the default setting, if heating mode exists together with
the water heating mode, the heat pump gives priority to heating. In that case, water heating can only realized with e-heater of the
water tank. Inversely, the heat pump gives priority to water heating and switches to heating after finishing water heating.

Emergency mode

:

this mode is only available for heating and water heating. When the outdoor unit stops due to malfunction, enter

the corresponding emergency mode; as to heating mode, after entering the emergency mode, heating can only be realized through e-
heater of the indoor unit. When the setting outflow temperature or indoor temperature is reached, the e-heater of indoor unit will stop
running; as to water heating mode, the e-heater of indoor unit stops while the e-heater of water tank runs. When the setting temperature
or water tank is reached, the e-heater will stop running.

Quick

water

heating

:

in quick water heating mode, the unit runs according to the water heating control of heat pump and the e-

heater of water tank runs at the same time.

Содержание GSR-M4-DC/M

Страница 1: ...AND USER MANUAL EN 50 70 90 115 125 150 MONOBLOCK DC INVERTER HEAT PUMP GSR M4 DC M GSR M6 DC M GSR M8 DC M GSR M10 DC M GSR M12 DC M GSR M14 DC M GSR M16 DC M GSR M10 DC T GSR M12 DC T GSR M14 DC T...

Страница 2: ...bloc unit 15 19 Electric wiring work 33 8 2 1 Selection of installation location of monobloc unit 15 19 1 Wiring principle 33 8 2 2 Outline dimension of monobloc unit 16 19 2 Specification of power su...

Страница 3: ...ply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The appliance shall be installed in accordance with national wir...

Страница 4: ...ling WARRANTY PERIOD AND LIFE TIME Warranty is 2 years from the date of invoice unless other terms are agreed separately Service life of the heat pump is 10 years this period can be change according t...

Страница 5: ...r wire connection Never damage the electric wire or use the one which is not specified Otherwise it may cause overheating or fire Before cleaning please cut off the power supply Otherwise it may cause...

Страница 6: ...ith flammable gas R32 For repairs strictly follow manufacturer s instructions only Be aware that refrigrants not contain odour Read specialist s manual If a stationary appliance is not fitted with a s...

Страница 7: ...of PCB for users cut off power means to stop supplying power to the unit Don t directly expose the unit under the corrosive ambient with water or dampness Don t operate the unit without water in water...

Страница 8: ...entering water pressures Maximum entering water pressures Cooling 0 05MPa 0 25MPa Heating Water heating The range of external static pressures at which the appliance was tested add on heat pumps and...

Страница 9: ...isible and legible Markings and signs that are illegible shall be corrected refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which ma...

Страница 10: ...tion equipment Intrinsically safe components do not have to be isolated prior to working on them Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this wil...

Страница 11: ...of the Operating Principle Flow switch Expansion Vessel Automatic exhaust valve Note the swimming pool solar kit and water mixing accessory are optional parts When they are required please contact the...

Страница 12: ...nsed With the help of wired controller the outflow temperature can meet the user s requirement Through the control of valve the high temperature water in the system is connected with the coil pipe of...

Страница 13: ...setting corresponding time to meet the requirement of disinfection mode the function will start After the setting temperature is reached this mode will terminate Weather dependent Operation this mode...

Страница 14: ...re enough water flow rate and by pass valve should be installed at the collector Notes a In this case three way valve should be installed and should be complied with installation of this manual b Sani...

Страница 15: ...ctric heater Under floor Coil Fan Coil Sanitary water tank Fan Coil CASE 3 Connecting Sanitary Water Tank Under floor Coil and FCU 7 Main Components GSR M4 DC M GSR M6 DC M GSR M8 DC M 3 wa y value Hi...

Страница 16: ...pressor is used to reduce vibration during transport Before commissioning they must be removed otherwise it would lead to unnecessary faults When foot brackets have been removed the fastening screws m...

Страница 17: ...16 8 2 2 Outline dimension of monobloc unit GSR M4 DC M GSR M6 DC M GSR M8 DC M GSR M10 DC M GSR M12 DC M GSR M14 DC M GSR M16 DC M GSR M10 DC T GSR M12 DC T GSR M14 DC T GSR M16 DC T...

Страница 18: ...d the unit from 4 directions Included angle between the rope when hanging and moving must be 40 below to prevent center of the unit from moving 2 Adopt M12 bolts components to tighten feet and under f...

Страница 19: ...SR M8 DC M GSR M10 DC M GSR M12 DC M GSR M14 DC M GSR M16 DC M GSR M10 DC T GSR M12 DC T GSR M14 DC T GSR M16 DC T 1 Take away the original rubber rings replace the long tail rubber rings of accessory...

Страница 20: ...bited in the maintenance area and th no smoking warning board should be hanged nameplate Check whether the appliance mark is in good condition Replace the vague or damaged warning mark llowed to be op...

Страница 21: ...djust its output based on the actual load 9 2 Water volume and expansion vessel pressure Note a The expansion vessel is 2 liter and 1 5bar pre pressurized for 4 6 8kW unit 3 liter and 1 5bar per b pre...

Страница 22: ...2 m Adjustment is not necessary 1 Pre set pressure needs to be adjusted according to the above formula 2 Check if the water volume is lower than the maximum water volume with help of the above figure...

Страница 23: ...n factor of water the difference between the expansion factor of the original water temperature and that of highest water temperature 10 Remote Air Temperature Sensor Water expansion factor in differe...

Страница 24: ...t 1 Uncover the front cover of indoor unit and open the control box 2 Identify the power specification of the thermostat if it is 230V find terminal block XT5 as NO 22 24 and block XT6 as NO 33 34 Oth...

Страница 25: ...Closed type should be connected to wire ON and wire N for valve closing in cooling mode ON Line signal for Normal Open type from PCB to 2 way valve OFF Line signal for Normal Closed type from PCB to 2...

Страница 26: ...ral signal from the main board to the 3 way valve 14 Other Thermal Other thermal is allowed for the equipment and controlled in such a way that the mainboard will output 230V when outdoor temperature...

Страница 27: ...2 Optional water temperature sensor connecet to AP1 CN16 Step 3 Wired controller setting Other thermal should be selected with if necessarily from COMMISION FUNCTION then set switch on outdoor tempera...

Страница 28: ...loc unit in series Moreover an accessory called optional water temperature sensor 5 meter length shall be installed at the same time The optional electric heater could be 1group or 2 group and only wo...

Страница 29: ...d Discharging of Refrigerant The unit has been charged with refrigerant before delivery Overcharging or undercharging will cause the compressor to run improperly or be damaged When refrigerant is requ...

Страница 30: ...sure that the detector is not a potential source of ignition and is suitable for the refrigerant used 4 Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be...

Страница 31: ...ater pipe and water outlet of water tank with PPR pipe Safety check valve Tap water Note 1 For safe use of water water outlet inlet of water tank must connect with a certain length of PPR pipe L 70 R2...

Страница 32: ...et of unit with circulating inlet of water tank 4 Installation of water inlet outlet pipes of the water tank safety check valve filter and cut off valve must be installed for the water inlet pipe acco...

Страница 33: ...rm heat preservation of waterway system meanwhile pay more attention to valves and pipe joints Ensure enough thickness of insulated cotton If necessary install heating device for pipeline to prevent t...

Страница 34: ...4 DC T 16 5 x 2 5 GSR M16 DC T 16 5 x 2 5 Model 220 240VAC 1Ph 50Hz 380 415VAC 3Ph 50Hz Note a Leakage Switch is necessary for additional installation If circuit breakers with leakage protection are i...

Страница 35: ...3 4 power supply 5 CN18 Interface to the variable frequency water pump CN19 Interface to the variable frequency water pump CN15 20K temperature sensor inlet water CN15 20K temperature sensor outlet w...

Страница 36: ...pin 12V FB 1 2 3 4 signals 5 power supply to EXV2 pipe electric expansion valve 1 4 pin driving impulse output 5 pin 12V T_SENSOR2 1 2 environment 3 4 discharge 5 6 suction 1 2 hole pipe temperature...

Страница 37: ...ction AC L Live line input N Neutral line input L OUT Live line output N OUT Neutral line output COMM Communication U To compressor phase U V To compressor phase V W To compressor phase W CN16 CN15 CN...

Страница 38: ...terface to the variable frequency water pump CN19 Interface to the variable frequency water pump CN15 20K temperature sensor inlet water CN15 20K temperature sensor outlet water CN15 20K temperature s...

Страница 39: ...pin 12V FB 1 2 3 4 signals 5 power supply to EXV2 pipe electric expansion valve 1 4 pin driving impulse output 5 pin 12V T_SENSOR2 1 2 environment 3 4 discharge 5 6 suction 1 2 hole pipe temperature...

Страница 40: ...AC L L OUT Live line input of the filter board 2 N N OUT Neutral line input of the filter board 3 L1 1 To PFC inductor brown line 4 L1 2 To PFC inductor white line 5 L2 1 To PFC inductor yellow line 6...

Страница 41: ...3 4 power supply 5 CN18 Interface to the variable frequency water pump CN19 Interface to the variable frequency water pump CN15 20K temperature sensor inlet water CN15 20K temperature sensor outlet w...

Страница 42: ...ly to EXV1 pipe electric expansion valve 1 4 pin driving impulse output 5 pin 12V FB 1 2 3 4 signals 5 power supply to EXV2 pipe electric expansion valve 1 4 pin driving impulse output 5 pin 12V T_SEN...

Страница 43: ...ut line L2 F drive board L3 F L3 F power supply output line L3 F drive board L3 F X9 to the grounding line Silk Screen Specification W Connector to the compressor phase W U Connector to the compressor...

Страница 44: ...43 21 Electric Wiring The wiring diagram stuck to the unit always prevails 1 GSR M4 DC M GSR M6 DC M GSR M8 DC M 2 GSR M10 DC M GSR M12 DC M GSR M14 DC M GSR M16 DC M...

Страница 45: ...44 3 GSR M10 DC T GSR M12 DC T GSR M14 DC T GSR M16 DC T 22 Terminal Board 1 GSR M4 DC M GSR M6 DC M GSR M8 DC M...

Страница 46: ...45 2 GSR M10 DC M GSR M12 DC M GSR M14 DC M GSR M16 DC M 3 GSR M10 DC T GSR M12 DC T GSR M14 DC T GSR M16 DC T...

Страница 47: ...C T GSR M16 DC T Name Rated Frequency Rated coil voltage Rated working voltage for the main circuit Rated working current for the main circuit AC contactor 50Hz 220V 220V 25A KM1 12 13 14 380 415V 3N...

Страница 48: ...nk thermostat is special one it means the water tank thermostat is not all pole disconnection thermostat the water tank thermostat must be connected in series to the circuit of the water tank contacto...

Страница 49: ...Are the nilometer of water tank water temperature indicator controller manometer pressure relief valve and automatic discharge valve etc installed and operated properly 9 Does power supply accord wit...

Страница 50: ...heck the phase sequence before start up to avoid reverse rotation of the compressor which may damage the unit 4 Apply the universal electric meter to measure the insulation resistance between each out...

Страница 51: ...imely contact with authorized service center Notes The water pressure gage is installed in the returning water line in the unit Please adjust the hydraulics system pressure according to next item 1 If...

Страница 52: ...be suitable for the recovery of flammable refrigerants In addition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect c...

Страница 53: ...and operate in accordance with manufacturer s instructions h Do not overfill cylinders No more than 80 volume liquid charge i Do not exceed the maximum working pressure of the cylinder even temporari...

Страница 54: ...ahallesi kumpas cad No 10 Tuzla stanbul T RK YE Telefon 90 216 394 09 85 86 87 Faks 90 216 394 24 91 www gassero com retici Sat c Firma GREE ELECTRIC APPLIANCES INC OF ZHUHAI West Jinji Rd Qianshan Zh...

Отзывы: