To change the final pressure setting of the Celtic Regulator N (blanketing pressure), adjust the setup screw or
replace the spring according to the table below, using the option best suitable for the application.
Shutter Spring (Piston)
Inlet Pressure
Outlet pressure regulating spring
(On the sensor diaphragm)
01.52.46B
Up to 1.5 bar
01.53.02
01.53.02A
01.53.02B
01.53.02C
01.52.46C
1.5 to 4.0 bar
05 / 30 mmWC
10 / 50 mmWC
15 / 80 mmWC
30 / 150 mmWC
01.52.46D
3.5 to 8.0 bar
-
05 / 30 mmWC
10 / 55 mmWC
30 / 130 mmWC
To replace the setup spring, proceed as follows (FIG.2):
Remove the cap (47) of the adjusting screw.
Release the adjusting screw (rendering the spring unloaded)
Remove the hood (52) from the housing, which will come out together with the adjusting screw.
Remove the spring adjuster (45) and the spring (3) to be replaced. Insert the new spring, the spring
adjuster and the hood in the reverse order of the disassembly.
Readjust the final blanketing pressure of the Celtic N regulator.
Lock the adjusting screw with the lock nut and replace the cap.