Mechanical PCU Option
Pump Control EXPMUX CPU Board
Page 84
MDE-4319A TopKAT Fuel Managment System Installation Manual · November 2005
Switches 1 through 4 denote the address. This is factory set and may not have to be corrected.
The table below gives the switch settings for the address selections.
8
Switches SB-5 through SB-8 are not relevant to the operation of this unit and should be set to
Closed.
9
The settings for switch bank SC (1 through 4) determine when the pump control unit begins
counting pulses for a particular pump. When a switch is open, the PCU begins counting pulses
when the corresponding pump is activated. When a switch is closed, as it should be for most
configurations using mechanical pumps, the PCU does not count pulses for the corresponding
pump until the mechanical reset has completed. The table below gives the switch settings for
SC-1 through SC-4.
10
In switch bank SC, 5 through 8, only switch 6 and 8 are active. Switch SC-6 is the Deadman
Timer Switch. If enabled, the pump control unit must be polled at least every 15 seconds by
the TopKAT. If it fails to sense a poll at that time, it turns all relays off. If Reset Complete
Mode is used on any pump on a particular PCU, the deadman timer should be disabled.
Switch SC-8 enables the test mode allowing the basic PCU functions to be tested without the
use of a site controller.
Address
SB-1
SB-2
SB-3
SB-4
ADDR1
ADDR2
ADDR3
ADDR4
1
Closed
Closed
Closed
Closed
2
Open
Closed
Closed
Closed
3
Closed
Open
Closed
Closed
4
Open
Open
Closed
Closed
5
Closed
Closed
Open
Closed
6
Open
Closed
Open
Closed
7
Closed
Open
Open
Closed
8
Open
Open
Open
Closed
9
Closed
Closed
Closed
Open
10
Open
Closed
Closed
Open
11
Closed
Open
Closed
Open
12
Open
Open
Closed
Open
13
Closed
Closed
Open
Open
14
Open
Closed
Open
Open
15
Closed
Open
Open
Open
16
Open
Open
Open
Open
Switch
Function
SC-1
Mode pump 1
Open = Normal, Closed = Reset Complete
SC-2
Mode pump 2
Open = Normal, Closed = Reset Complete
SC-3
Mode pump 3
Open = Normal, Closed = Reset Complete
SC-4
Mode pump 4
Open = Normal, Closed = Reset Complete