he SeeLeveL II consists of a sender bar, a donut shaped float, 

a  fiber  optic  interconnect  cable,  and  a  display.    The  sender 

bar is mounted vertically in the tank with the float sliding up and 

down around it in accordance with the fluid level.  The sender bar 

sends the fluid level and temperature information via fibre optic 

cable to the display.  The temperature is the average value of the 

sensors below the fluid level, so the air temperature above the 

fluid is ignored.  The display shows the level, volume, temperature 

and alarm status to the user, and provides alarm and remote 

communication outputs.

The Sender and Float:

  The sender bar consists of a flexible 1/2 

inch diameter polyethylene pipe with a head at the top end where 

the fibre optic cable connects.  It is secured at the top of the tank 

by a compression fitting just below the head, and is secured at the 

bottom of the tank by an anchor fitting.  The compression fitting 

provides the seal where the sender exits the tank, and the anchor 

keeps the sender bar vertical in the tank. This mounting system 

allows the sender bar to be removed from the top of the tank for 

servicing without having to go into the tank.

The float is molded from polyethylene for high chemical resistance 

and durability.  The float contains magnets which activate reed 

switches inside the sender bar to indicate the level of the fluid, 

which is measured with a resolution of 1/4” throughout the tank.  

The activated switches are detected by a microprocessor at the 

top of the bar.  The use of a digital rather than analog sensing 

technique lowers power consumption to permit battery operation 

and ensures high accuracy with no drift or degradation.  The 

sender optically transmits the level and temperature information 

every two seconds via an LED located in the head, so the LED 

will appear to flash once every two seconds.  There are electronic 

temperature sensors located every 16 inches inside the bar, one 

sensor is sampled and a new average is obtained every 2 seconds.  

For a 50 foot long bar, there are 37 sensors, which would require 

74 seconds to sample all of them.  All of the sensors below the 

fluid level are included in the average; the sensors above the fluid 

level are excluded, so the average temperature is for the fluid only, 

not the air or vapor above the fluid.  The microprocessor operates 

from a 3.6 volt lithium battery module giving over 5 years of life, 

the battery module can be field replaced with simple hand tools.

CHAPTER 2 - SYSTEM DESCRIPTION

Содержание SeeLevel II 900-D4D DUAL

Страница 1: ..._____________________________________________________ TANK NUMBER ______________________________________________________________________ MINIMUM TANK READOUT _________________________________________________________ MAXIMUM TANK READOUT _________________________________________________________ ALARM HIGH VOLUME ALARM LOW VOLUME Normally Open or Normally Closed ALARM 1 NO NC ALARM 2 NO NC ALARM 3 N...

Страница 2: ...APTER 3 KEYPAD OPERATING INSTRUCTIONS 10 CHAPTER 4 INSTALLATION GUIDE 19 CHAPTER 5 TROUBLESHOOTING GUIDE 20 CHAPTER 6 MASTER CODE 21 CHAPTER 7 SPECIFICATIONS 22 CHAPTER 8 SERVICE WARRANTY INFORMATION 23 GARNET SEELEVEL II TM Tank Fluid Monitor MODEL 900 D4 SINGLE 900D4D Manual_v3 3 12 Dec 2019 ...

Страница 3: ... for the float and can operate over a range of product temperatures from 40 C to 90 C 40 F to 194 F The temperature is sensed by semiconductor temperature probes spaced every 16 inches along the inside length of the bar The SEELEVEL II components are weatherproof to allow installation in any environment Most monitor functions operate entirely on internal batteries so external power is not required...

Страница 4: ...without having to go into the tank The float is molded from polyethylene for high chemical resistance and durability The float contains magnets which activate reed switches inside the sender bar to indicate the level of the fluid which is measured with a resolution of 1 4 throughout the tank The activated switches are detected by a microprocessor at the top of the bar The use of a digital rather t...

Страница 5: ...conduit for protection and it can be disconnected at both ends for servicing The type of fibre used has a 1 0 mm core diameter and an outer jacketed diameter of 2 2 mm It can be cut with a sharp knife no stripping or other special preparation is needed The Display The display receives the optical information from the sender translates the signal into volume and temperature information to show to t...

Страница 6: ...e LCD shows Inch and the other LCDs show the product level in inches for each of the volumes If the ALARMS button is pressed the temperature LCD shows ALAr and the fluid temperature 2 LCD shows the current alarm status based on the product level and the alarm set points Alarms 1 to 4 are shown as 1234 on the LCD if the alarm output is active the number is shown and if the alarm output is inactive ...

Страница 7: ...t 100mA at 24 volts These outputs are for connecting to an external alarm system which has been designed to work with this type of output The alarm outputs and ground are available at a terminal block inside the display enclosure WARNING The use of alarm points is entirely at the owner s risk due to the nature of connecting external horns or lights the reliability of external horns or lights and t...

Страница 8: ...pment may read slightly different than the gauge display Display 1 5 V Outputs The display has four 1 5V signals available at terminal blocks inside the display enclosure Two of the 1 5V outputs are volume they derives their output values from the two volume displays 1 0V corresponds to an empty tank for example 0 barrels and the user sets the full scale 5 0V value of the output For example if the...

Страница 9: ... degradation in accuracy with it Consequently the remote equipment may read slightly different than the gauge display DisplayEnclosure Theentiredisplayisenclosedinaweatherproof fiberglass enclosure with a hinged cover This provides all weather operation and easy access to the internal batteries The enclosure must always be kept tightly closed when not changing batteries to prevent water damage to ...

Страница 10: ... permits access to functions 5 and 6 only 13 To enter the 8 digit master code which permits authorized personnel to set the user codes and to access functions 7 to 10 Since the operation of the gauge can be severely compromised by improper keypad use there are security features incorporated into the gauge These security features also allow the owner of the tank to better manage rentals and billing...

Страница 11: ...ions which saves the tank owner the trouble of having to travel out to the tank to program the gauge The initial code out the door is 123456 this can be changed with the master code 3 Master Code this is an eight digit code used by management and the installer to set the user codes and the gauge display calibration It provides complete access to all gauge functions It cannot be changed it is coded...

Страница 12: ...emperature format Stor will be shown momentarily 7 TANK ID MENU Press FAST UP to access the Tank id menu This allows the tank to be given a four digit number The feature will be fully implemented in the future 8 EXIT MENU To exit the programming mode press FAST UP to access the exit menu the display will show SUC donE Press ENTER Prog donE will be shown momentarily and the gauge will return to nor...

Страница 13: ...e to a point quickly there are five speed buttons press 4 to increase by 10 inches press 1 to decrease by 10 inches press 5 to increase by 50 inches press 2 to decrease by 50 inches or press 0 to set the alarm point to zero To toggle the polarity alternate between closed and open press the decimal point button 5 Press ENTER to store the new alarm setting Stor will be shown momentarily 6 To access ...

Страница 14: ...ns being pressed a blank value will be stored and the 4 20 output will not function properly 11 EXIT MENU To exit the programming mode press FAST UP until the exit menu is accessed the display will show LUC donE Press ENTER Prog donE will be shown momentarily and the gauge will return to normal operation 12 If a menu is left without pressing ENTER any change to that menu item will NOT be stored If...

Страница 15: ...number is for reference only it is never shown during normal operation If the top right display shows tohi then the fluid level has been set to over 960 inches which is taller than the tallest possible sender bar 8 Determine where to set the offset If the tank is empty measure from the bottom of the tank to the middle of the vertical part of the float for interface displays measure to the top floa...

Страница 16: ... 16 foot tank then the volume per inch would be 1000bbls 16ft 12in ft 5 2083333 bbls in The gauge resolution is 5 208333 4 1 3 bbls per 1 4 In this case displaying only even barrels would be appropriate since we cannot resolve less than one barrel So the volume per inch to write down for this example would be 5 2083 no decimal is used by the gauge in this case 13 The gauge requires exactly 8 digit...

Страница 17: ...e is no decimal for XXXX or XXXX they will be ignored and not displayed if entered It is important to maintain the same decimal location for the entire table since the calibration value and decimal location for the 1 4 1 2 and 3 4 inch points may be incorrect between the points where the decimal point is moved 20 Press ENTER to store the entered volume calibration and to advance to the next inch v...

Страница 18: ...ramming mode press FAST UP until the exit menu is accessed the display will show CAL donE Press ENTER Prog donE will be shown momentarily and the gauge will return to normal operation The software release number is shown in this menu as well for example rEL 3 00 25 If a menu is left without pressing ENTER any change to that menu item will NOT be stored If no button is pressed for 3 minutes then th...

Страница 19: ...Page 19 900D4D Manual CHAPTER 4 INSTALLATION GUIDE Since installation details can vary widely with application contact Garnet Instruments Ltd for installation details ...

Страница 20: ...If the display reads erratically check for water inside the sender head or display To test a sender bar 1 Make sure the sender is flashing once every 2 seconds from the optical connector If not replace the battery module If this doesn t help the sender is dead and must be replaced 2 If the sender is flashing plug a piece of fibre into the sender optical connector and the other end of the fibre int...

Страница 21: ...Page 21 900D4D Manual CHAPTER 6 MASTER CODE The Master code is available upon request Note This code should not be revealed to anyone who does not need to know ...

Страница 22: ...n show up to 959 7 inches of level Temperature display can show from 40 C to 100 C in 1 increments or from 40 F to 212 F Displayed temperature is an average of all immersed sensors Alarm display shows active alarms Battery display shows display and sender battery conditions Display batteries Four alkaline AA batteries power all display functions expected lifetime is 3 to 4 years Batteries can be r...

Страница 23: ...s are the only warranties expressed or implied upon which products are sold by Garnet and Garnet makes no warranty of merchantability or fitness for any particular purpose in respect to the products sold Garnet products or parts thereof assumed to be defective by the purchaser within the stipulated warranty period should be returned to the seller local distributor or directly to Garnet for evaluat...

Страница 24: ......

Отзывы: