4.0  TROUBLESHOOTING GUIDE

SYMPTOM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

A)  Water downstream of dryer

1.  Residual free moisture remaining in 

downstream pipelines

2.  Air bypass system is open

3.  Inlet and Outlet connections are reversed

4.  Air lines downstream of dryer are exposed 

to temperatures below the dew point.

5.  Excessive free moisture (bulk liquid) at 

dryer inlet.

6.  Condensate not being drained 

 

Drain mechanism is clogged or 

inoperative.

 

Drain line is restricted or frozen.

 

Electric drains-timer not set to allow for 

sufficient condensate removal. 

7.  Dryer overloaded resulting in elevated dew 

point.

8.  Refrigeration system not functioning

Blow out system with dry air

Check valve positions

Check for correct connection

Insulate or heat trace air lines exposed to low 

ambients or dry air to lower dew point

Install separator ahead of dryer

Replace drain mechanism if inoperative.

Open drain line.

Electric drains-reset time so that all liquid is 

discharged

Check inlet air temperature and pressure, flow 

rate (compressor capacity) and ambient air or 

water temperature.

See D below

B)  High pressure drop across dryer

1.  Excessive air flow

2.  Freezing of moisture in evaporator 

because of refrigeration system fault

3.  Separator filter element clogged

Check flow rate

See D below

Replace filter element

C)  Dew point indicator in red area

1.  Dryer overloaded resulting in high air 

outlet temperature

2.  Refrigeration system not functioning 

properly resulting in high air outlet 

temperature 

See A 7

See D below

D)  Refrigeration system not functioning 

properly

1.   Power on light off

2.  Compressor on light off

3.  Refrigeration compressor cycles on 

and off 

a.  Power failure

b.  Line disconnect switch open

c.  Blown fuses, open breaker

d.  Faulty wiring, loose terminals

a.  ON/OFF switch is “OFF”

b.  Line disconnect switch open

c.  Blown fuses, open breaker

d.  Faulty wiring, loose terminals

a.  High or low ambient conditions

b.  Air-cooled - Dirty, clogged condenser fins, 

obstructed flow across condenser, faulty 

fan motor or fan control switch.

Check for power to unit

Close disconnect switch

Check for continuity

Have electrician check electrical connections.

Turn switch “ON”

Close disconnect switch

Check for continuity

Have electrician check electrical connections

Check min./max. temperature ranges

Clean condenser and check for free air flow, if 

problem persists contact qualified refrigeration 

repairman or manufacturer’s service 

department.

Содержание SPX FLOW DHP Series

Страница 1: ...ed Type Compressed Air Dryer Models DHP130 DHP200 DHP300 DHP500 DHP750 DHP1000 FOR M NO 5003971 R EVI S ION 07 2016 R EAD AN D U N D E R STAN D TH I S MAN UAL PR IOR TO OPE RATI NG OR S E RVICI NG TH...

Страница 2: ...UIDE 7 5 0 REFERENCE 8 5 1 Sizing 8 5 2 Engineering Data 9 6 0 DIMENSIONS WEIGHTS 10 7 0 DRAWINGS 11 7 1 Process Gas Refrigeration Flow Diagram Models DHP130 and DHP200 11 7 2 Process Gas Refrigeratio...

Страница 3: ...lant It was received in good condition by the carrier and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you in sist that...

Страница 4: ...he dryer inlet outlet connections from the piping External piping must be properly supported The installation of a flexible connection or vibration dampener within the air gas stream prior to the drye...

Страница 5: ...nection NOTE Strainer and water regulating valve are supplied on water cooled models 1 4 Electrical Connections IMPORTANT Use copper supply wires only A Dryer is designed to operate on the volt age ph...

Страница 6: ...temperature 120 F 49 C D Maximum ambient temperature Air cooled models 110 F 43 C Water cooled models 130 F 54 C E Minimum ambient temperature 40 F 4 C Condensate Draining Drain Push to Test On Off Sw...

Страница 7: ...e NOTE Failure to perform step 3 within 25 seconds of com pleting step 2 will cause the unit to revert back to the previous setting NOTE In the event of a brief or extended period of power loss the un...

Страница 8: ...e separator filter elements become loaded with solid particles 2 Procedure for Separator Filter Element Replacement THIS FILTER IS A PRESSURE CONTAINING DEVICE DEPRESSURIZE BEFORE SERVICING a Isolate...

Страница 9: ...ss dryer 1 Excessive air flow 2 Freezing of moisture in evaporator because of refrigeration system fault 3 Separator filter element clogged Check flow rate See D below Replace filter element C Dew poi...

Страница 10: ...emperature and 100 F ambient temperature and 60 Hertz operation MODEL RATED FLOW scfm m3 hr DHP130 DHP200 DHP300 DHP500 DHP750 DHP1000 130 200 300 500 750 1000 221 340 510 850 1275 1700 Table 2 Capaci...

Страница 11: ...N A 1 2 2 0 2 8 3 3 Electrical Data Nominal Voltage 115 1 60 208 230 3 60 Min Max Voltage 104 127 187 253 Input Power Rated Flow watts 932 1280 1255 1962 2910 4120 Rated Load Amps 10 2 13 0 7 5 10 4...

Страница 12: ...651 32 15 817 32 15 817 32 15 817 32 15 817 C 2 50 63 5 2 50 63 5 2 50 63 5 2 50 63 5 2 50 63 5 2 50 63 5 D 23 62 600 23 62 600 30 15 766 30 15 766 30 15 766 30 15 766 E 17 62 448 17 62 448 30 15 766...

Страница 13: ...IEF VALVE PRE COOLER REHEATER CONDENSATE DRAIN AUTOMATIC ELECTRIC DRAIN SERVICE VALVE MANUAL DRAIN AIR AIR HEAT EXCHANGER HIGH TEMPERATURE SWITCH OPTIONAL EVAPORATOR CARTRIDGE TYPE MOISTURE SEPARATOR...

Страница 14: ...ESS FITTING FITTING ACCESS PRESSURE VALVE RELIEF HEAT EXCHANGER REHEATER PRE COOLER AIR AIR SWITCH STANDARD CONDENSER DETAIL OPTIONAL WATER COOLED TYPE CARTRIDGE SEPARATOR MOISTURE OPTIONAL GAUGE OPTI...

Страница 15: ...2 L1 N L1 CONT 1 T1 T2 TO GROUND STUD PE T1 T2 TO GROUND STUD PE FAN 1 HARNESS C 1 FAN 1 MTR2 FPS 1 COMPRESSOR MTR1 DRAIN NEUTRAL COMPRESSOR ON L1 L1 N L1 1 1 N L1 1L1 N 1 N GROUND STUD 6 7 J5 3 5 4 1...

Страница 16: ...1 L3 L2 PE HEATER HARNESS 1L2 L3 TB2 TB2 PE T3 T2 H1 HEATER 1 FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 18 REF SHEET 01 LINE 19 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE TB1 L1 L2 L3...

Страница 17: ...10 09 08 06 05 04 03 X X 02 01 00 FROM SHEET 01 X X X X THERMISTER CONTROL BOARD DRAIN NEUTRAL DRAIN LINE THERMISTER NEUTRAL 3 N N HPS 1 LINE 1 1 1 TB2 GRN YELLOW DRAIN HARNESS DRAIN HARNESS PE TB2 3...

Страница 18: ...L3 TB2 TB2 PE T3 T2 H1 HEATER 1 FAN 2 HARNESS FPS 2 FAN 2 REF SHEET 02 LINE 12 REF SHEET 01 LINE 20 03 10 11 12 09 08 07 06 05 04 L3 L3 L3 L2 L2 02 01 00 PE L1 L1 L1 L3 L2 TB1 L1 L3 L2 CONT 1 DISCONN...

Страница 19: ...08 06 05 04 03 X X 02 01 00 FROM SHEET 01 X X X X THERMISTER CONTROL BOARD DRAIN NEUTRAL DRAIN LINE THERMISTER NEUTRAL 3 N N HPS 1 LINE 1 TB2 GRN YELLOW DRAIN HARNESS DRAIN HARNESS PE TB2 3 TB2 PE X 3...

Страница 20: ...18 7 6 Wiring Diagram Models DHP300 through DHP1000 575 460 3 60 Transformer Pack...

Страница 21: ...3232829 3232830 5002924 3232832 3232829 3232830 5002924 3232832 Low Refrigerant Pressure Switch 4006372 4006372 4006372 4006372 4006372 4006372 4006372 4006372 High Refrigerant Pressure Switch 3230764...

Страница 22: ...20 NOTES...

Страница 23: ...part THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARR...

Страница 24: ...low com www spxflow com deltech Improvements and research are continuous at SPX FLOW Inc Specifications may change without notice ISSUED 07 2016 Form No 5003971 Revision F COPYRIGHT 2016 SPX FLOW Inc...

Отзывы: