5.0 REFERENCE
5.1 Sizing
Determining dryer capacity at actual operating conditions
To determine the maximum inlet flow capacity of a dryer at vari
-
ous operating conditions, multiply the rated capacity from Table
1 by the multipliers shown in Table 2.
Example:
How many scfm can an air-cooled model DHP300
handle when compressed air to be dried is at 350 psig and
90°F; ambient air temperature is 80°F?
Answer: 300 x 1.19 x 1.12 = 400 scfm.
Table 1. Rated Capacity
Rated capacity (scfm) @ 725 psig inlet pressure, 100°F inlet
temperature, and 100°F ambient temperature and 60 Hertz
operation.
MODEL
RATED FLOW
(scfm)
m
3
/hr
DHP130
DHP200
DHP300
DHP500
DHP750
DHP1000
130
200
300
500
750
1000
221
340
510
850
1275
1700
Table 2. Capacity Adjustment Factors for Air Inlet
Temperature and Pressure
INLET PRESSURES
INLET TEMPERATURES
(psig)
(barg)
80°F
27°C
90°F
32°C
100°F
38°C
110°F
43°C
120°F
49°C
300 to 725
21 to 50
1.49
1.19
1.00
0.83
0.72
Table 3. Capacity Adjustment Factors for Ambient Air
Temperature
AMBIENT
TEMPERATURE
°F (°C)
CAPACITY
ADJUSTMENT
FACTOR
80°F (27°C)
1.12
90°F (32°C)
1.06
100°F (38°C)
1.00
110°F (43°C)
0.94
Water-cooled
(85°F, 29.4°C
cooling water)
1.15
Table 4. Capacity Adjustment Factors for Electrical
Frequency
50 Hertz
60 Hertz
0.83
1.00