1.0 INSTALLATION

1.1  Location

A. Air compressor intake - Locate air compressor so that

contaminants potentially harmful to the dryer (e.g.

ammonia) are not drawn into the air system.

1. Location - locate the dryer so that the coolest

ambient air possible will be drawn across

the condenser.

B. Free air flow - Do not block either side of the

cabinet. Leave 12 inches (305 mm) on each side of

cabinet for free air flow.

1.2 Mounting

A. Models RHP50 and larger - Feet are supplied as

standard. Feet may be removed if floor or shelf

mounting is desirable.

B. Models RHP13 and RHP20 include wall mounting

bracket. See Illustration.

1.3 Piping connections

A. Air Inlet - Connect compressed air line from air

compressor to air inlet.

Refer to Serial Number Tag for maximum

working pressure. Do not exceed unit’s Maximum

Working Pressure.
NOTE: For maximum capacity, install unit in air

system at highest pressure possible (e.g. before

pressure reducing valves).
NOTE: For maximum capacity, install unit at coolest

compressed air temperature possible.
NOTE: Maximum inlet compressed air temperature:

120°F (49°C).  If inlet air exceeds this temperature,

precool the air with an aftercooler.

)

AIR INLET

AIR OUTLET

AIR OUTLET

AIR INLET

MODELS RHP64

RHP100

MODELS  RHP13 & RHP20

AIR INLET

MODELS RHP93

RHP178

MODEL  RHP50

AIR OUTLET

)

AIR OUTLET

AIR INLET

B.  Air Outlet - Connect air outlet to downstream

 air lines.

C. By-pass piping - If servicing the unit without

interrupting the air supply is desired, piping should

include inlet and outlet isolation valves and an air by-

pass valve.

D. Drain - It is advisable to connect the automatic drain

outlet to the condensate drainage system.

NOTE: Drain discharge is at system pressure. Drain

line should be anchored to prevent whipping.

E. Water cooled models - cooling water inlet and outlet

1. Connect inlet water line to strainer.

2. Connect outlet piping.

NOTE: Strainer and water regulating valve are supplied on

water cooled models.

1.4  Electrical connections

A. Dryer is designed to operate on the voltage, phase,

and frequency listed on the serial number tag.

B. Dryer is supplied with an electrical cord and plug.

NOTE: Refrigeration condensing unit is designed to

run continuously and should NOT be wired to cycle

on/off with the air compressor.

Wall Mounting Bracket For Models RHP13 & RHP20

Hanger

Lockwasher

3/8" Bolt

Locking Clip

Cabinet

Mounting Slot

Wall

SERIAL NUMBER TAG

* Models RHP50, RHP64, RHP93, RHP100 and RHP178 only

SUCTION PRESSURE
GAUGE*

ON/OFF SWITCH*

Содержание RHP Series

Страница 1: ...re containing device Do not exceed maximum operating pressure as shown on equipment serial number tag Make certain equipment is depressurized before servicing 2 ELECTRICAL This equipment requires elec...

Страница 2: ...he air with an aftercooler AIR INLET AIR OUTLET AIR OUTLET AIR INLET MODELS RHP64 RHP100 MODELS RHP13 RHP20 AIR INLET MODELS RHP93 RHP178 MODEL RHP50 AIR OUTLET AIR OUTLET AIR INLET B Air Outlet Conne...

Страница 3: ...continuous duty service However when solenoid is energized for a long period the coil enclosure becomes hot and can be touched with the hand for only an instant This is a safe operating temperature C...

Страница 4: ...tenance A Filter Sleeve Replacement The separator assembly contains a coalescing filter sleeve which requires replacement yearly or when excessive pressure drop is experienced across the dryer whichev...

Страница 5: ...serial number tag Suction Pressure Setting controlled by hot gas by pass valve psig barg 31 5 2 2 31 5 2 2 Air Flow Across Condenser cfm 60 Hz 50 Hz 235 196 235 196 Minimum Maximum Operating Condition...

Страница 6: ...2 4 17 5 Branch Circuit Fuse Size amps 15 20 25 Watts 35 F Evaporator 100 F Ambient 465 815 1060 Overload Thermal Current Auto reset Nominal Voltages 208 230 1 60 Max Min Voltage 253 207 253 187 253 1...

Страница 7: ...1 2 64 2 1 2 64 OUTLET FAN AIR FLOW INLET B FRONT VIEW TOP VIEW C MINIMUM CLEARANCE FOR FREE AIR FLOW BOTH SIDES E D M A L RIGHT SIDE VIEW POWER ON GREEN HIGH TEMP RED ELECTRICAL BOX SEPARATOR INSULAT...

Страница 8: ...1 589 819 495 737 394 41 38 92 64 311 52 81 230 NPT RHP178 500 23 3 16 32 1 4 19 1 2 29 15 1 2 1 5 8 1 1 2 2 1 4 2 1 2 2 1 2 3 7 8 9 1 16 3 4 1 1 2 589 819 495 737 394 41 38 57 64 64 98 230 NPT RHP100...

Страница 9: ...on functioning fan motor or fan control switch c Water cooled models Cooling water temperature too high or flow too low faulty water regulating valve clogged water strainer Blow out system with dry ai...

Страница 10: ...28 2 G4140 227 17 G4140 227 17 G4140 227 17 Condenser air cooled G4130 110 26 G4130 110 26 G4130 110 26 G4130 111 18 G4130 111 18 G4130 111 18 Dryer Strainer G4130 165 14 G4130 165 14 G4130 165 14 G41...

Страница 11: ...4130 138 13 G4130 138 13 G4130 138 13 G4130 138 13 G4130 138 13 Condenser water cooled G4130 112 11 G4130 112 11 G4130 134 36 Water Control Valve G4130 145 20 G4130 145 20 G4130 145 22 Water Strainer...

Страница 12: ...paired or replaced under warranty shall be warranted for the unexpired portion of the warranty applying to the original product The foregoing is the exclusive remedy of any buyer of the manufacturer s...

Отзывы: