background image

5

ELECTRICAL SCHEMATIC

Models RHP13 & RHP20

Min.- Max. Inlet Air Pressure ( compressed air at inlet to dryer )                                                             

  5 psig (0.3 bar) - See Serial Number Tag for Maximum Pressure

Max. Inlet Air Temp. (compressed air at inlet to dryer)

120°F (49°C)

Min.-Max. Ambient Temperature

35°F (1.7°C) - 110°F (43°C)

        Refrigeration System Data

RHP13

RHP20

Compressor Type

                                                             Hermetic - Resistance Start, Induction Run - Non-Cycling

Refrigeration Compressor Horsepower

1/6                                                      1/5

BTU/HR - Refrigeration Only @ 35°F Evaporator & 100°F Ambient

60 Hz / 50 Hz

1010 / 842

1380 / 1150

Outlet Air Temperature (nominal at rated conditions)

40°F (4.4°C)

40°F (4.4°C)

Refrigerant Type

R-134a

R-134a

Refrigerant Charge

See dryer serial number tag

Suction Pressure Setting (controlled by hot gas by-pass valve) - psig (barg)

31.5 (2.2)

 31.5 (2.2)

Air Flow Across Condenser (cfm)

60 Hz / 50 Hz

235 / 196

235 / 196

Minimum - Maximum Operating Conditions

              1)   115-1-60

115/1/60

208-230/1/60

220-240/1/50

115/1/60

208-230/1/60

220-240/1/50

Max.- Min. Voltage

127-104

253-187

264-198

127-104

253-187

264-198

Rated Load Amps

3.4

1.8

1.6

3.9

2.1

1.8

Locked Rotor Amps

18.0

8.5

8.7

22.0

13.7

10.7

Minimum Circuit Ampacity

4.0

2.2

2.0

4.7

2.6

2.2

Branch Circuit Fuse Size (amps)

15

15

15

15

15

15

Watts @ 35°F Evaporator & 100°F Ambient

280

280

223

290

290

257

Overload

Thermal & Current (Auto reset)

               Electrical Data

Model RHP13

Model RHP20

ENGINEERING DATA

LEGEND

1LT - Power On Light
2LT - High Temperature Light
SR - Start Relay
MTR - Compressor
FM - Fan Motor
HTS - High Temperature Switch
OL - Overload
SOL - Electric Drain Valve

Содержание RHP Series

Страница 1: ...re containing device Do not exceed maximum operating pressure as shown on equipment serial number tag Make certain equipment is depressurized before servicing 2 ELECTRICAL This equipment requires elec...

Страница 2: ...he air with an aftercooler AIR INLET AIR OUTLET AIR OUTLET AIR INLET MODELS RHP64 RHP100 MODELS RHP13 RHP20 AIR INLET MODELS RHP93 RHP178 MODEL RHP50 AIR OUTLET AIR OUTLET AIR INLET B Air Outlet Conne...

Страница 3: ...continuous duty service However when solenoid is energized for a long period the coil enclosure becomes hot and can be touched with the hand for only an instant This is a safe operating temperature C...

Страница 4: ...tenance A Filter Sleeve Replacement The separator assembly contains a coalescing filter sleeve which requires replacement yearly or when excessive pressure drop is experienced across the dryer whichev...

Страница 5: ...serial number tag Suction Pressure Setting controlled by hot gas by pass valve psig barg 31 5 2 2 31 5 2 2 Air Flow Across Condenser cfm 60 Hz 50 Hz 235 196 235 196 Minimum Maximum Operating Condition...

Страница 6: ...2 4 17 5 Branch Circuit Fuse Size amps 15 20 25 Watts 35 F Evaporator 100 F Ambient 465 815 1060 Overload Thermal Current Auto reset Nominal Voltages 208 230 1 60 Max Min Voltage 253 207 253 187 253 1...

Страница 7: ...1 2 64 2 1 2 64 OUTLET FAN AIR FLOW INLET B FRONT VIEW TOP VIEW C MINIMUM CLEARANCE FOR FREE AIR FLOW BOTH SIDES E D M A L RIGHT SIDE VIEW POWER ON GREEN HIGH TEMP RED ELECTRICAL BOX SEPARATOR INSULAT...

Страница 8: ...1 589 819 495 737 394 41 38 92 64 311 52 81 230 NPT RHP178 500 23 3 16 32 1 4 19 1 2 29 15 1 2 1 5 8 1 1 2 2 1 4 2 1 2 2 1 2 3 7 8 9 1 16 3 4 1 1 2 589 819 495 737 394 41 38 57 64 64 98 230 NPT RHP100...

Страница 9: ...on functioning fan motor or fan control switch c Water cooled models Cooling water temperature too high or flow too low faulty water regulating valve clogged water strainer Blow out system with dry ai...

Страница 10: ...28 2 G4140 227 17 G4140 227 17 G4140 227 17 Condenser air cooled G4130 110 26 G4130 110 26 G4130 110 26 G4130 111 18 G4130 111 18 G4130 111 18 Dryer Strainer G4130 165 14 G4130 165 14 G4130 165 14 G41...

Страница 11: ...4130 138 13 G4130 138 13 G4130 138 13 G4130 138 13 G4130 138 13 Condenser water cooled G4130 112 11 G4130 112 11 G4130 134 36 Water Control Valve G4130 145 20 G4130 145 20 G4130 145 22 Water Strainer...

Страница 12: ...paired or replaced under warranty shall be warranted for the unexpired portion of the warranty applying to the original product The foregoing is the exclusive remedy of any buyer of the manufacturer s...

Отзывы: