13-17-621 Page 17
o
If the pressure is between the Warning and Fault pressure settings, it will be displayed in
yellow:
o
If the pressure is above the Fault pressure setting, it will be displayed in red:
2. The Discharge Temperature gauge shows the compressor airend discharge temperature.
o
If the temperature is below the Minimum Start Temperature setting, it will be displayed in
red.
o
If the temperature is between the Minimum Start Temperature setting and 3
℃
(5.4
℉
)
above the Minimum Start Temperature, it will be displayed in yellow.
o
If the temperature is above the Minimum Start Temperature plus 3
℃
(5.4
℉
) and below
the Warning temperature setting, it will be displayed in green.
o
If the temperature is above the Warning temperature setting and below the Fault
temperature setting, it will be displayed in yellow.
o
If the temperature is above the Fault temperature setting, it will be displayed in red.
3. The
View Schematic
button is used to navigate to the Schematic screen. This provides a
graphical representation of the machine operation and status.
4. The Control Settings Indicators area of the screen shows the current status of the control settings
that control machine operation and starting / stopping. Pressing anywhere within this area of the
screen will navigate to the Control Settings screen which can be used to adjust these settings.
o
Remote Halt
: The Remote Halt indicator reflects the setting of Remote Halt Mode on the
control settings screen. If the Remote Halt Mode is Disabled, the indicator will show Off. If
the remote halt mode is Timed or Immediate, the indicator will show On.
o
Timer Control
: The Timer Control indicator reflects the setting of Timer Start Enable on
the Control Settings screen.
o
Auto Restart
: The Auto Restart indicator reflects the setting of Auto Restart Enable on
the Control Settings screen.
5. The Status Message Bar displays information about the current machine status. If a fault or
warning is active, red or yellow attention indicators will illuminate on the bar.