13-17-621 Page 101
As shown in the Figure above
, Max Start Pressure
and
Heavy Startup
settings are grayed out and the
user can’t make changes to them.
4.7.2.1 Max Start Pressure:
The
Max Start Pressure
setting defines the maximum start pressure in the reservoir before the motor will
be allowed to start.
4.7.2.2 Heavy Startup:
The
Heavy Startup
setting defines the maximum pressure that will be allowed to be built up in the reservoir
during the acceleration process, if this pressure is exceeded a heavy startup fault will occur.
4.7.2.3 Minimum Start Temperature:
The
Minimum Start Temperature
setting is the temperature the compressor needs to be at before the
motor will start. Figure 138 below shows the setting of
Minimum Start Temperature
as
39°F
.
Figure 138: Minimum Start Temperature
4.7.2.4 Discharge Temperature Warning:
The
Discharge Temperature Warning
setting defines the temperature value where an over temperature
warning will be triggered. This applies to both the discharge and separator temperature values. The warning
may not be set above the value of the discharge temperature fault. Figure 139 below shows the setting of
Discharge Temperature Warning
at
224°F
.
Содержание Governor TEN014980