TROUBLE 

DISPLAY 

POSSIBLE CAUSE 

REMEDY 

LOW PRESSU

RE IN T

HE LI

NE

 

 

 

Ice formation in the evaporator. 

Check the probe; if the trouble persists, replace it. 

Check the electronic control board; if the trouble persists, 
replace it. 

Contact our Service Centre to check the gas charge. 

 

Clog. 

Check if the compressed air inlet/outlet is connected properly. 

Check if the connecting tubing is clogged; in case proceed 
accordingly. 
Check if any valves are closed. 

Check the condition of any filter. 

 

Air flows continuously through the 
condensate drainage. 

Drainage solenoid valve jammed, clean or replace it. 

Verify the condensate drainage times set on the electronic control 
board (C8 and C9). 
Check the signal from the control board: if it is continuous, 
replace the control board. 
Check the no loss condensate drain; if the trouble persists, 
replace it. 

IMPORTANT

The temperature control probe is extremely delicate. Do not remove the probe from its position. In case of any kind of 
problem, please contact your local Gardner Denver distributor  

Pic.3 drain solenoid valve 

 

 

 

 

 

 

When it is necessary: 

 

Clean the mesh filter of the 
condensate drainage system. 

 

Clean the filter mesh.

 

 

Pic.4 
Optional: No loss condensate drain (NLD) 

 

 

 

 

Electronic  drain  discharge  NLD  is  the  new  discharger  applicable  to  any 
compressed  air  systems.  It  eliminates  the  condensate  without  wasting 
compressed air. 
Electronic  drain  discharge  starts  automatically,  without  the  need  of  any 
adjustment. The condensate discharge occurs to the use of an electronic sensor, 
which detects the amount of condensate in the integrated water collecting tank. 
The  level  sensor  drives  start  and  duration  of  the  drainage,  so  preventing  any 
wasting of compressed air.  
At the end of installation, put the system under pressure and push the TEST key 
repeatedly to eliminate the air bubbles contained in the discharger inlet fittings. 
Please refer to the attached CD of the discharger for complete instructions. 
To this discharger will be applied the NLD warranty conditions.

 

Filter mesh 

Cleaning of the drain solenoid valve 

Содержание GDD4F

Страница 1: ...02 2022 Copyright 2022 Gardner Denver All rights reserved 1 10 DIRECT EXPANSION COMPRESSED AIR DRYERS Operators Manual GDD4F GDD7F GDD9F GDD12F GDD18F GDD24F GDD30F GDD37F GDD43F GDD50F GDD60F GDD80F...

Страница 2: ......

Страница 3: ...lation 4 3 START UP 3 1 Control panel 4 3 1 1 Keys function 5 3 1 2 Condensate discharge parameters programming 6 3 1 3 Anomaly warning 6 3 1 4 Remote signalling alarm 7 3 2 Before start up 7 3 3 Star...

Страница 4: ...Cod 710 0138 72 00 Rev 10 12 2021 Copyright 2021 Gardner Denver All rights reserved...

Страница 5: ...o the risk of electric shock Condensate drain point Rotation direction of the fan Pay particular attention to the risk of moving parts Explosion risk Lifting point Don t lift from this point Attention...

Страница 6: ...re enters counterflow the initial air air exchanger and it is reheated by the inlet hot air with the consequence of energy recovering and also reduction of the relative humidity contained in the outf...

Страница 7: ...attempt to lift heavy objects without proper lifting equipment i e crane hoist slings or fork truck Lifting any unit without proper lifting equipment may cause serious injury Use fork lift channels wh...

Страница 8: ...isolation switch if present The control panel will show the message OFF indicating that the line and control voltages are available Start sequence The dryer will initially start by pressing and holdi...

Страница 9: ...t point it increases the displayed value of one unit per second during the first 10 seconds than of one unit every 0 1 sec ON OFF Pressed it activates or deactivates the dryer When the dryer is deacti...

Страница 10: ...the dryer WARNING FOR USER IT S FORBIDDEN TO ATTEMPT TO MODIFY THE OTHER CONFIGURATION PARAMETERS OF THE ELECTRONIC CONTROLLER WITHOUT AUTHORIZATION AND COLLABORATION OF Gardner Denver S AUTHORIZED DI...

Страница 11: ...ng the first working hours 3 3 START UP The operations specified below must be performed after the first start up and at each start up after a prolonged inactive period of time due to maintenance oper...

Страница 12: ...ryer Replace elements as needed YEARLY OR EVERY 2000 HOURS OF OPERATION Check if the flexible tube used for condensate drainage is damaged and replace it if necessary Check if all connecting pipes are...

Страница 13: ...essure switch Reset the high pressure switch Problems with cabling or with the electronic control board Check the cabling and the electronic control board if the trouble persists replace them Activati...

Страница 14: ...xtremely delicate Do not remove the probe from its position In case of any kind of problem please contact your local Gardner Denver distributor Pic 3 drain solenoid valve When it is necessary Clean th...

Страница 15: ...y mains 4 3 DECOMMISSIONING All work on the dryer may only be carried out by specialist personnel Follow this procedure if you need to shut down the dryer Stop the device and permanently isolate it fr...

Отзывы: