6. Preparations for commissioning
32
Recommended supply cable cross-sections and fuses
Compressor type
Supply voltage
[V]
Installed nominal
motor power
[kW]
Fuse protection
(slow-blow fuse)
[AgL]
Line cross section
at 30°C
[mm
2
]
50-Hz-Compressors
ESM 30
220V
380V
400V
30
160
100
80
3x70PE35
4G35
4G25
ESM 37
220V
380V
400V
37
200
100
100
3x95PE50
4G35
4G35
ESM 45 - ESM 50
220V
380V
400V
45
200
125
125
3x95PE50
4G50
4G50
60-Hz-Compressors
ESM 30
230V
380V
460V
30
160
100
80
3x70PE35
4G35
4G25
ESM 37
230V
380V
460V
37
160
100
100
3x70PE35
4G35
4G35
ESM 45 - ESM 50
230V
380V
460V
45
200
125
100
3x95PE50
4G50
4G35
Notes on the table:
We do not know the cable type used by you, its length
and the installation conditions (temperatures, grouping).
The table above can therefore only be regarded as a
guideline.
The supply cable cross-sections given in the table
comply with VDE 0298, part 4 - table 13, column 7.
(Rubber hose line at 30 °C/86 °F and max. line length of
50 m). In the case of differing conditions (line length,
temperature and grouping), establish the cross sections
in accordance with DIN VDE 0298, part 4 or BS7671
taking into account the cable type.
Important
If local regulations are stricter than the values
specified above, observe the stricter regulations.