3.0  MAINTENANCE

3.1 Condenser coil

A.

Air-cooled - clean off accumulated dust and dirt monthly.
A factory mounted blow gun is provided for this pur-
pose.

B.

Water-cooled - clean strainer monthly, more often if
required. Shut off water, remove small plug to relieve
pressure, then remove large plug to remove strainer.
Clean strainer and replace.

3.2 Moisture separator/Oil filters

A.

When to replace the Separator/Filters

Replace filter element when pressure drop across dryer is
excessive or annually.

Dryers have the option of one or two stages of filtration.
The direction for servicing the top stage applies to both
the top stage in a two-stage arrangement and the single
stage in a single stage dryer.

When removing liquids at rated flow conditions, the
pressure drop will be 5 psi (0.35 bar), or less, across the
entire dryer. An increase in pressure drop will occur only
as the separator/filter elements become loaded with
solid particles. It is recommended, for maximum filtration
efficiency, the separator/filter elements be replaced
when the pressure drop across the dryer exceeds 10 psi
(0.7 bar), or every 12 months, whichever occurs first.

B.

Description of the Separator/Filter Assembly

The separator/filter assembly consists of: the separator
shell assembly (1), the upper shell cap (2), the upper shell
coupling  and gasket (3), the upper piping coupling and
gasket (4), the element retainer plate (5), and the separa-
tor/filter elements (6).

C.

Replacement of the Separator/Filters

Depressurize the unit before servicing. Failure

to do this may result in injury. The unit must be depressurized
before the couplings are removed.

a.

For normal element replacement, the only assembly
component that must be removed is the upper shell
cap. Remove the insulation from the upper shell cap.

Check to be sure the unit is depressurized.

b.

Remove the two bolts on the upper shell coupling
(3) and the upper piping coupling (4). Remove the
couplings, exposing the gaskets.

c.

Slide the upper piping gasket up on to the upper
piping. Slide the upper shell gasket down on to the
separator shell (1). The upper shell cap (2) should now
be free and removable.

d.

Remove the upper shell cap (2).

e.

Remove the element retainer plate (5).

f.

Remove the separator/filter elements (6) by simply
lifting them off of the element sealing posts (1b).
Discard the old elements.

g.

Inspect the inside surfaces of the separator shell (1),
the element seal plate (1a), and the element sealing
posts (1b).

Gasket

Coupling
Half

Grooved Shell

Grooved Upper 
Shell Cap

Bolts

3 & 4

NOTE: If the inside surfaces require additional cleaning or
inspection, the entire shell assembly(1) can be removed by
disassembling the lower shell coupling and gasket.

h.

Lubricate the new separator/filter element o-ring
seals according to the element package instructions.

i.

Install the new elements by carefully pushing them
on to the element sealing posts (1b).

j.

Reinstall the element retainer plate (5).

k.

Replace the upper shell cap (2).

l.

Inspect the upper shell cap gasket and the upper
piping gasket and apply a thin coat of lubricant to
the outside and to the sealing lips of these gaskets.

m. Slide the gaskets into position, centering them

between the coupling grooves.

n.

Replace the upper shell cap coupling (3) and the
upper piping coupling (4). Tighten the bolts evenly
and alternately.

Uneven tightening may cause the gaskets to

pinch and not seal! Gasket damage may result!

o.

Reinstall the insulation.

p.

Slowly repressurize the dryer.

q.

Inspect the assembly for air leaks.

NOTE: Further disassembly is not required or recommended
for maintenance.

Содержание 9VXRD Series

Страница 1: ...00 9VXRD3000 SERVICE DEPARTMENT 724 746 1100 INSTRUCTION MANUAL CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 9 ENGINEE...

Страница 2: ...ge be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found...

Страница 3: ...nches 610 mm of clearance in front of dryer E Standard units are designed to operate in ambients Air cooled 45 to 110 F 7 to 43 C Water cooled 45 to 130 F 7 to 54 C F Dryer is designed to operate at a...

Страница 4: ...3 4 C At installation install the petcock on the bulkhead fitting for the manual drain For manual draining convenient dryer depressurization and EDD service a three way valve at the bottom of the mois...

Страница 5: ...yer disconnect switch provided by others sec NEC 24 hours before refrigeration compressor is started Never use the disconnect switch to shut down the dryer for a extended period of time except for rep...

Страница 6: ...restored after power interruption 7 To reinstitute SCHEDULE RUNNING If compressor is scheduled to be off push Set Run button to restart schedule If compressor is scheduled to be on push On Off button...

Страница 7: ...edule Driven or Dryer Driven modes 1 De energize unit and disconnect the power supply to the dryer 2 Remove the cabinet panels as necessary to provide access to the Monitor panel 3 On the rear of the...

Страница 8: ...t that must be removed is the upper shell cap Remove the insulation from the upper shell cap Check to be sure the unit is depressurized b Remove the two bolts on the upper shell coupling 3 and the upp...

Страница 9: ...t 200 psig and 100 F ambient air temperature is 80 F and a 45 F dew point temperature is desired Answer 1 000 x 1 22 x 1 12 x 1 2 1 640 scfm TABLE 2 Air capacity correction factors Multipliers MODEL 1...

Страница 10: ...ATICS 380 420 3 50 NOTES 1 575 3 60APPLICATIONS FANMOTORS ARE460 3 60ANDARESUPPLIEDFROMEQUIPMENT MOUNTEDTRANSFORMER 2 FANCONTACTORS FANMOTORS FANPRESSURESWITCHES ANDFANTRANSFORMERS 575VONLY ARENOTUSED...

Страница 11: ...11...

Страница 12: ...Dimensions in mm Inlet Outlet Height Width Depth Weight Model Connections A B C Lb kg 1000 4 1 720 780 1250 4 85 2159 48 1207 49 1232 1 740 789 1500 4 1 850 839 1750 6 2 000 907 2000 6 2 100 953 2500...

Страница 13: ...7 9 40 5 47 6 50 74 1 92 5 89 7 Branch Circuit Fuse Size amps 60 60 70 80 125 150 125 Watts 35 F Evaporator 100 F Ambient 8 480 9 860 12 140 12 780 18 960 22 100 25 640 Resistance ohms Three phase Tot...

Страница 14: ...at trace air lines exposed to low ambients or dry air to lower dew point Install separator ahead of dryer See C below See C below See C below Check flow rate See C below Replace filter element Check f...

Страница 15: ...38 31 G4130 138 31 G4130 138 31 G4130 138 31 G4130 138 31 High refrigerant Pressure switch G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 Fan cutout switch...

Страница 16: ...ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAM...

Отзывы: