IMPORTANT: READ PRIOR TO STARTING THIS EQUIPMENT

1.0 INSTALLATION

1.1 Location

A.

For typical placement in a compressed air system, see
drawing.

B.

Air compressor intake–Locate air compressor so that
contaminants potentially harmful to the dryer (e.g.
ammonia) are not drawn into the air system.

C.

Dryer should be installed in a moderately heated, well
ventilated area. Avoid locations immediately adjacent to
cold exterior windows or walls, or adjacent to high
temperature ovens or boilers.

D.

Clearances: Free air flow
Models 1000 to 1500:

Front 24 inches (610 mm)
Back 36 inches (915 mm)
Sides 24 inches (610 mm)
Top 36 inches (915 mm)

Models 1750 to 3000

Front 24 inches (610 mm)
Back 36 inches (915 mm)
Sides 24 inches (610 mm)
Top 36 inches (915 mm)

Service - To facilitate maintenance leave 24 inches
(610 mm) of clearance in front  of dryer.

E.

Standard units are designed to operate in ambients:
Air-cooled: 45 to 110

°

F (7 to 43

°

C).

Water-cooled: 45 to 130

°

F (7 to 54

°

C).

F.

Dryer is designed to operate at all altitudes - no adjust-
ment for altitude is required.

G.

The installation of a flexible connection prior to the dryer
is recommended to prevent possible damage from
vibration.

NOTE: Outdoor installation–Standard units are designed for
indoor installation. Contact manufacturer if installing
outdoors.

Aftercooler

Separator

Dryer

Compressor

Electrical 
Entry

RS232 
Port

Electric 

Demand 

Drain (EDD)

3-way Valve 
for Manual 
Draining

Moisture 
Separator
(single stage)

Control 

Panel

FRONT VIEW

OUT

IN

Air Outlet

Air Inlet

Condenser

BACK VIEW

See Exploded 

View "A"

Manual Drain 

Valve (Optional

)

Automatic Drain 

Valve (Optional

)

Manual 

Drain Valve

 

Automatic 

Drain Valve 

EXPLODED VIEW  "A"

DRAIN VALVE CONNECTIONS

Quick 

Release

Door Locks

Optional
Oil Removal
Filter (2 stage)

Water Outlet

Water Inlet

Содержание 9VXRD Series

Страница 1: ...00 9VXRD3000 SERVICE DEPARTMENT 724 746 1100 INSTRUCTION MANUAL CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 5 3 0 MAINTENANCE 8 SIZING 9 ENGINEE...

Страница 2: ...ge be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Damage When a shipment has been delivered to you in apparent good order but concealed damage is found...

Страница 3: ...nches 610 mm of clearance in front of dryer E Standard units are designed to operate in ambients Air cooled 45 to 110 F 7 to 43 C Water cooled 45 to 130 F 7 to 54 C F Dryer is designed to operate at a...

Страница 4: ...3 4 C At installation install the petcock on the bulkhead fitting for the manual drain For manual draining convenient dryer depressurization and EDD service a three way valve at the bottom of the mois...

Страница 5: ...yer disconnect switch provided by others sec NEC 24 hours before refrigeration compressor is started Never use the disconnect switch to shut down the dryer for a extended period of time except for rep...

Страница 6: ...restored after power interruption 7 To reinstitute SCHEDULE RUNNING If compressor is scheduled to be off push Set Run button to restart schedule If compressor is scheduled to be on push On Off button...

Страница 7: ...edule Driven or Dryer Driven modes 1 De energize unit and disconnect the power supply to the dryer 2 Remove the cabinet panels as necessary to provide access to the Monitor panel 3 On the rear of the...

Страница 8: ...t that must be removed is the upper shell cap Remove the insulation from the upper shell cap Check to be sure the unit is depressurized b Remove the two bolts on the upper shell coupling 3 and the upp...

Страница 9: ...t 200 psig and 100 F ambient air temperature is 80 F and a 45 F dew point temperature is desired Answer 1 000 x 1 22 x 1 12 x 1 2 1 640 scfm TABLE 2 Air capacity correction factors Multipliers MODEL 1...

Страница 10: ...ATICS 380 420 3 50 NOTES 1 575 3 60APPLICATIONS FANMOTORS ARE460 3 60ANDARESUPPLIEDFROMEQUIPMENT MOUNTEDTRANSFORMER 2 FANCONTACTORS FANMOTORS FANPRESSURESWITCHES ANDFANTRANSFORMERS 575VONLY ARENOTUSED...

Страница 11: ...11...

Страница 12: ...Dimensions in mm Inlet Outlet Height Width Depth Weight Model Connections A B C Lb kg 1000 4 1 720 780 1250 4 85 2159 48 1207 49 1232 1 740 789 1500 4 1 850 839 1750 6 2 000 907 2000 6 2 100 953 2500...

Страница 13: ...7 9 40 5 47 6 50 74 1 92 5 89 7 Branch Circuit Fuse Size amps 60 60 70 80 125 150 125 Watts 35 F Evaporator 100 F Ambient 8 480 9 860 12 140 12 780 18 960 22 100 25 640 Resistance ohms Three phase Tot...

Страница 14: ...at trace air lines exposed to low ambients or dry air to lower dew point Install separator ahead of dryer See C below See C below See C below Check flow rate See C below Replace filter element Check f...

Страница 15: ...38 31 G4130 138 31 G4130 138 31 G4130 138 31 G4130 138 31 High refrigerant Pressure switch G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 G4130 138 28 Fan cutout switch...

Страница 16: ...ORAL OR STATUTORY AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAM...

Отзывы: