INSTALLATION

LOCATION

The unit is designed for outdoor installation and shall not be placed in a
totally enclosed area such as a shed or a garage unless ventilation is
provided to ensure adequate air exchange for proper operation.
Recirculation of cold discharge air back into the evaporator coil will greatly
reduce heating capacity and efficiency of the unit and void the compressor
warranty.

The heater should be located as close as practical to the existing pool pump
and filter to minimize water piping length.  The use of 90

°

 bends and short

radius elbows in the water piping should be limited to keep water pressure
drop to a minimum.

Your heater features an up-flow fan for quiet operation.  Air is pulled
through the evaporator coil and discharged through the top grill.  At least 4
feet clearance should be allowed above the unit for unrestricted air
discharge.  The unit must not be installed under a porch.  Any side of the
unit should be located at least 12 inches from a wall or other obstruction for
unrestricted air intake and service access.

Mount the unit on a flat, level surface, preferably a concrete or fabricated
slab.  The unit should be completely isolated from the building foundation or
wall to prevent the possibility of sound or vibration transmission into the
building.  The base of the unit may be used to fasten to if local codes
require securing the unit to the slab.

Make sure that there are no sprinkler heads near or directly spraying into
the heater.  Cap off or redirect heads as needed.

WIND TIE DOWNS

The unit can be strapped down using the Gulfstream strap kit. Attach a
strap to each side and anchor to the deck.

Содержание Gulfstream

Страница 1: ...G F Manufacturing Swimming Pool Heat Pump Owner s Installation Operations Manual 5005001B Version 2 02 ...

Страница 2: ...Up 6 Bonding 7 Water Chemistry Maintenance 8 Heat Pump Features 9 Heat Pump Operation 10 Control On Off 10 Pool Spa Modes 10 Changing Set Point Temperature 11 Heater Running Time 11 Keypad Lockout 11 Defrost Cycle 11 Condensate Draining 11 Care Maintenance 12 Cleaning 12 Winterizing 12 Troubleshooting 13 Service 15 ...

Страница 3: ...ic resistance heater does it can heat your swimming pool or spa for up to 80 less cost than these other less efficient methods As with all pool heating methods you are advised to utilize a pool cover at night and when the pool is not in use The pool cover should be used if the night temperature is 15 F 8 C less than the desired pool temperature This will keep evaporation the greatest source of hea...

Страница 4: ... please take a moment and jot down the following information If you should ever need to call us for service or a question we will need this information Model Number ___________________________________ Serial Number ___________________________________ Purchase Date ___________________________________ Dealer Name Address Phone _______________________ _________________________________________________...

Страница 5: ...ough the evaporator coil and discharged through the top grill At least 4 feet clearance should be allowed above the unit for unrestricted air discharge The unit must not be installed under a porch Any side of the unit should be located at least 12 inches from a wall or other obstruction for unrestricted air intake and service access Mount the unit on a flat level surface preferably a concrete or f...

Страница 6: ...t excessive pump head pressure is not indicated The recommended flow rate is 50 gpm through the heater For questions on multiple heater installations please contact our engineering department Multiple unit installations should always be in parallel circuits ELECTRICAL HOOK UP CAUTION The main power disconnect must be off before opening the access panel It is recommended that the wiring of your hea...

Страница 7: ...l equipment On some older pools this substructure bond wire may not exist In this case a 6 to 8 ft copper rod must be driven into the ground near the pool equipment and all electrical and metal components must be bonded to the rod A bonding lug is furnished on the side of the control box of the heater for the bond wire to be attached Warranty will be void if system is not properly bonded Attach Bo...

Страница 8: ... 7 8 1 time per week Chlorine Concentration 1 0 to 3 PPM 1 time every 2 to 3 days Total Alkalinity 80 to 120 PPM 1 time every 2 to 3 weeks Total Dissolved Solids Below 2400 PPM 1 time per month Calcium Hardness 200 to 300 PPM 1 time per month The location of the chemicals introduction to your system is also critical to the heater s life If an automatic in line chlorinator or brominator is used it ...

Страница 9: ...pabilities ULTRA QUIET The unit is equipped with a low RPM fan motor in combination with a deep drawn venturi to ensure whisper quiet operation HIGH EFFICIENCY The heat pump utilizes the latest in compressor technology to produce the highest efficiency available when coupled with the over sized enhanced fin evaporator coil EASE OF INSTALLATION The unit is equipped with easy to install hand tighten...

Страница 10: ...he two settings with the POOL SPA button located on the control When power is applied to the control it will turn on in the previous mode whether it is Pool Heat or Spa Heat When water is flowing through the unit and the water temperature meets the specified set point condition the control will initiate a heat cycle If you do not have a spa you can use the spa thermostat as a second temperature se...

Страница 11: ...y When you first run your heater it may need to run continuously for 24 to 48 hours to get the pool up to the desired temperature KEYPAD LOCKOUT While in any mode the user can lockout the keypad by pressing and holding the POOL SPA button for 6 seconds When the keypad lockout has been enabled all buttons are disabled and the control will operate in whatever mode it was in when the lockout occurred...

Страница 12: ...ny build up Keep the drain holes in the base free of debris to assure proper condensate drainage Your heat pump s cabinet is made from a maintenance free rust free plastic that is UV resistant It will last for years and any dirt or dust may simply be wiped away with a cloth or sprayed off with a water hose The use of a product such as Armor All will restore its natural luster DO NOT USE CLEANERS T...

Страница 13: ...ITION POSSIBLE CAUSE POSSIBLE SOLUTION Control Display Blank No power supply to heater Tripped breaker or blown fuse Control failure Reset breaker Replace fuse If problem persists call factory for service Control Displays LOW FLOW The pool pump is not on A valve is turned bypassing the water through the heater Clogged water line filter or pump impeller Internal water pressure switch failure Turn p...

Страница 14: ...N Water sensor malfunction or not connected Call factory for service Pool is heating slowly or not getting up to temperature Low or restricted water flow through the heater Leak in plumbing allowing air into the water flow It is cold outside Pump timer is not set for a long enough run time Pool is not being covered High wind speed over pool Pool area shaded Clean or replace filter Inspect and clea...

Страница 15: ...a service call If you still need help follow the instructions below Service can be obtained by calling us at 954 318 6900 When asking for help or service please provide a detailed description of the problem your heater s complete model number and serial number the purchase date and dealer purchased from This information will help us respond properly to your request Keep a copy of the sales receipt...

Отзывы: