7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
41
FCC Required Information
Basic System Module (BSM)
3.13 FCC Required Information
This equipment complies with Part 68 of the FCC Rules. The Ringer Equivalence Number (REN)
is listed in Section 3.10, while the FCC Registration Number is listed in Section 3.11. These
numbers must be provided to the telephone company, if requested.
3.14 Repairs
The 7100-D Digital Communicator does not contain any user-serviceable parts. The unit must be
returned to the factory for repair through an authorized Gamewell-FCI distributor.
3.15 Optional Accessories
3.15.1 LCD-7100 Serial Remote Annunciator
The LCD-7100 Serial Remote Annunciator provides an 80-character display and function keys for
the following:
•
The 80-character display shows all pertinent information except for menus.
•
Keypad functions are enabled only when the keylock is turned to the “Unlocked” position,
with the exception of the “Trouble Acknowledge” switch which silences the local audible
trouble sounder.
•
Operating LEDs provided are as follows:
•
The LCD-7100 is flush or surface-mounted on a standard 4-gang electrical box.
•
The 7100 Series control can accommodate up to five (5), remote LCD-7100 annunciators
which may be located up to 4,000 feet from the main control panel. Table 3.15.1 lists the
resistance limitations of the connecting circuit.
– “Alarm Acknowledge”
– “System Reset/Lamp Test”
– “Trouble Acknowledge”
– “System Drill Test”
– “Signal Silence”
–
– “Alarm”
– “Power Fault”
– “NAC #1 Silenced”
– “Supervisory”
– “System Silenced”
– “NAC #2 Silenced”
– “System Trouble”
Number
of
LCD-7100
Units
1 2 3 4 5
Maximum resistance of 24 VDC power circuit
(Ohms) to most distant LCD
70 38 24 17 4
Table 3.15.1 Resistance Limitations