Gamatronic Electronic Industries Ltd.
POWER+
SA
User Guide, Release 1.6
37
1.
Ensure that the lines coming into the UPS are equipped with circuit
breakers of the following capacity:
UPS output:
50A
Class C
Bypass output:
50A
Class C
AC input:
3x20A Class C
The following table gives the
required cable diameters
that must be used
when connecting the UPS. The table states the cable diameters in mm
2
.
AC output
Gnd, N, Ph
Bypass
input
Gnd, N, Ph
AC input
Gnd, N, R, S, T
Battery input
10 mm
2
10 mm
2
2.5 mm
2
6 mm
2
(Use the battery cable supplied by
Gamatronic.)
Using a screwdriver, remove the cable cover from the rear of the POWER+ SA.
The uncovered rear panel for the 3-1 configuration is shown in the next
illustrations.