Centric Installation Guide, rel. 2.8
65
10.3
Maintenance Procedures and Report
Record the values of all parameters checked and of measurements taken during the periodic maintenance
in the form below. Fax the completed form to Gamatronic at +972-2-582-8875.
1. UPS model and configuration
Company ______________________
_______________________________
Address _______________________________________
_______________________________________________
Site ___________________________
Phone ________________
E-mail _________________
Centric ____________________ kW
No. of UPS modules:
_____
No. of redundant UPS modules,
if any: _______
Type of maintenance: [ ]
Annual
[ ]
Semi-annual
[ ]
Quarterly
System S/N
(found on external sticker-label): ______________________________________
Technician Name _______________
_______________________________
Date
___________________
Signature
___________________________
2 . V i s u a l I n s p e c t i o n o f c a b i n e t
OK
[ ]
Not OK
[ ]
Comments ________________________________________________________
3 . E n v i r o n m e n t a l I n s p e c t i o n
Environmental
temperature
________
°
C
Ventilation
[ ]
OK
[ ]
Not OK
Air conditioning
[ ]
Yes
[ ]
No
Comments ________________________________________________________
_________________________
4 . D i s p l a y P a n e l s
LCD Display
[ ]
OK
[ ]
Not OK Comments ____________________________
LEDs
[ ]
OK
[ ]
Not OK Comments ____________________________
5 . V o l t a g e s
Verify that displayed dc voltages, rectifier input voltages, and inverter output voltages are showing proper values.
Verify the readings for the UPS as a whole
(“Menu option 1, System”, or on touch screen “Main menu >Status”)
and for each module
(“Menu option 2, UPS Module” or on touch screen “Main menu > Status > Modules”).
Dc voltages
(+)_______________ (-)_______________ (Total)_______________
Rectifier input
voltages
Volts: __________ __________ __________
Amperes: __________ __________ __________
Hertz: __________
Inverter output
voltages
Volts: __________ __________ __________
Amperes: __________ __________ __________
Hertz: __________
6 . S e r i a l N u m b e r / C l o c k a n d C a l e n d a r
Done
Verify that the UPS’s clock and calendar show the correct date and time.
If either the date or time are incorrect, enter the correct information and save.