TROUBLESHOOTING 

                            PROBLEM 

                               REPAIR CHECKLIST 

1.  No Flow. 

1.    Check the main shut-off valve. 

2.  Insufficient water flow. 

2.     Verify minimum 210 kPa flowing supply 

line pressure. 

     3. Insufficient water flow on eye/face 
         wash, however, shower is sufficient 

     3. a. Verify minimum 210 kPa flowing supply 

line pressure 

 
              b. Probable clogging of flow control due  
                  to inadequate line flushing. Unscrew 
                  eye/face wash head and remove the 
                  four screws to disassemble head. 
                  Clean flow control and reassemble  
                  Head. 
 
              c. Remove plug located on L 

– Strainer 

                  

using a 9/16” wrench to access  

clean filter screen. 

    4. Eye/face wash streams do not meet 
        desired eye level.  

     4.   Possible blocked flow control, see above 
           solution. Possible non-leveled eye/face 
           wash assembly 

   5. Water does not drain properly. 

     5.   Check your drain system for debris. Check 
           the main waste line of your building to see 
           if it does handle the capacity required for 
           the entire drainage system 

   6. Water leak between joints or fittings. 

     6.  Tighten loose connections. If leak persists, 
           the application of hot water will sometimes 
           reseat improperly applied joint compound. 
           After 30 minutes wait and retest. A 
           persistent leak will necessitate reassembly 
           and additional sealant. 

   7. Insufficient water flow from shower, 
       however, eye/face wash is sufficient. 

     7.   Probable clogging of flow control inside 
           showerhead.  Unscrew showerhead off of 
           elbow and clean rubber flow control. 

Отзывы: