Occasionally, when you fit a Status Monitored galvanic isolator, both of the
warning lights may glow straight away.

If both lights are illuminated on your galvanic isolator, you have AC earth
leakage.

You do NOT have a faulty isolator

. In fact, your isolator is alerting

you to a potentially dangerous situation that you may not previously have
been aware of.

There are two main types of earth leakage: Mains Leakage and Imprinted Leakage.

Mains Leakage

Mains  Leakage  happens  when  an  appliance,  cable  or  connection  has  poor
insulation resistance, and some of the circuit’s current “leaks” away to earth. If there
is sufficient leakage, the earth leakage circuit breaker, also known as the RCD, will
trip, disconnecting the supply.

At  lower  levels  of  leakage,  although  the  RCD  may  not  trip,  the  lights  on  your
galvanic  isolator  may  still  glow,  alerting  you  to  the  likelihood  of  earth  leakage.
Usually, an earth leakage fault will only get worse, so you should always take this
seriously and investigate.

No two electrical systems are the same, so it’s only possible to give the broadest
suggestions of how to locate any problem. Usually some detective work is required,
and this starts by switching off the main RCD on the boat. In most cases, this will
result in the lights on the isolator  going out. If not, there  is probably something
connected to the mains supply BEFORE the RCD.

Ensure  that  the  electrical  supply  is  disconnected
before  working  on  a  circuit,  and  remember  that  in
some systems, an auxiliary supply such as an inverter
may automatically kick in when the mains supply is
disconnected.  If  you  are  in  any  doubt,  you  should
entrust the work to a competent person.

!

A

ssuming the lights go out when the RCD is switched off, switch off ALL the
circuit

b

breakers, then switch the RCD back on. In most cases, the isolator’s

lights will stay off. You can then switch the circuit breakers back on one at a time
until the isolators lights come back on. The last circuit breaker you switched on has
the faulty circuit, or appliance connected to it.

Very rarely, even though all the circuit breakers (except the RCD) are switched off,
the  isolator  lights  will  remain  on.  In  this  case  you  will  need  to  disconnect  all
appliances, either by pulling out the plugs, or disconnecting any wired in appliances.
Do this one at a time, taking care to ensure that you don’t forget anything. As you
disconnect items, check the isolator lights. The last item you disconnect is the one
causing problems.

Model Gi-120/BK only

Содержание Gi-120/BK

Страница 1: ...oubt please consult a qualified electrician or call us We will be glad to Advise G i Tel 0757 807 3490 www galvanic isolator co uk Galvanic Isolator Gi 120 A Gi 120 BK Instructions G i IMPORTANT To pr...

Страница 2: ...he Isolator may be mounted to practically any flat surface The most secure method of mounting is to use the screw positions inside the isolator enclosure Alternatively it can be fixed using either a m...

Страница 3: ...gland nuts are tight To open the connectors please press clip see photo and twist connector body halves in opposite directions If in doubt please seek advice from a qualified person IMPORTANT To preve...

Страница 4: ...ive clear basic advice on how to resolve the problem Both Lights ON If both lights are ON this indicates AC leakage usually from the mains wiring or a connected appliance AC leakage can be a danger to...

Страница 5: ...is required and this starts by switching off the main RCD on the boat In most cases this will result in the lights on the isolator going out If not there is probably something connected to the mains...

Страница 6: ...ause of the way SMPSU s operate some of them leak power into the boat s earth wiring This can cause the galvanic isolators light to come on as the isolator correctly detects the leakage Imprinted Leak...

Страница 7: ...cates a possibility of AC mains voltage leakage Proceed with great care Danger of electrical shock If in doubt please consult a qualified electrician Unplug every appli ance connected to a socket in t...

Отзывы: