2. Installation / 3. Troubleshooting

2. Installation

The HEATER should be INSTALLED by an appropriately licensed installer. Installation must be confirmed in the warranty card. Due to its design, the heater 
must be installed VERTICALLY only. The heater must be connected directly to the water main system (with the capability of disconnecting it, e.g. for 
maintenance) of pressure not exceeding 0.6 MPa, whereas the minimal pressure must not be smaller than 0.1 MPa (approx. 1 at). In the case when the water 
main system pressure exceeds 0,6 MPa, it is necessary to reduce the pressure with a pressure reducing valve. The relief valve, such as the ZB8 FACH Cieszyn, 
must be installed on the cold water supply pipe, however relief valve equipped with the feature of reducing water pressure in the heater by redirecting it to 
the supply system, the water supply system within 5 m from the relief valve should sustain water temperature of +90°C. The discharge port of the relief valve 
must be opened to the atmosphere at all times. It is allowable to connect the heater in a manner providing several water outlet points. The heating coil of the 
water exchanger can be supplied from a low temperature water boiler protected in accordance with PN-91/B-02413, operating in an open system, or from a 
CH low temperature water boiler operating in a closed system (with a membrane expansion vessel) in accordance with PN-91/B-02414.

In order to protect the pumps, three-way valve and exchanger from dirt, a mesh-type filter shall be installed in the circuit. We recommend flushing of the 
entire heating system prior to installation. All connected branching shall be thermally insulated. If the system operation assumes the usable warm water 
heating priority using the three-way valve, we recommend following the installation instructions provided by the manufacturer of the three-way valve. 

To shut down the heater for a short period of time, turn off the power plug from the wall socket.

cold water

In order to drain the tank it is necessary to:
1. Close the cold water inlet before the valve or the relief group.
2. Open the „ZS” drain valve.
3. Open the hot water faucet so the air could flow through to the tank.

3. Troubleshooting

MALFUNCTION

CAUSE

METHOD OF REMOVAL

The relief valve does not open 
(also at the attempt of blowing-
through).

 

-

Relief valve is seized.

 

-

Clean or replace the valve.

Relief valve leaks.

 

-

The faying surface of the relief valve is 
contaminated or damaged.

 

-

Water pressure is too high.

 

-

Clean or lap the faying surface of the relief valve.

 

-

Use a pressure regulator.

DHW water is dirty.

 

-

Plenty of deposit in the tank, or the magne-
sium anode is used up.

 

-

Clean the tank of any deposit, or replace the magnesium anode 
(not covered by the warranty).

It is NECESSARY to use a dielectric connectors (made out of a plastic material - electrically nonconductive) between the hot and cold water 
connections and the installation's connections in order to avoid iron-copper contact, also in case where the relief group is connected directly 
to the tank. This extends the life of the water tank and prevents electrolysis phenomena, especially when the water is acidic (pH <7).

The symbol presented beside signifies that it is prohibited to dispose of worn electrical and electronic devices together with other waste. 
These products should be delivered to assigned waste collection points for waste processing. A proper recycling of electrical and electronic 
devices helps to protect the natural environment and prevents negative impact on human health.

Содержание SGW(S) Maxi 250

Страница 1: ...W S M 250 l 300 l 400 l 500 l 700 l 1000 l 300 l 400 l 500 l 300 l 400 l 500 l Titanium anode water heater is equipped with a magnesium anode as standard Please read the instructions carefully before...

Страница 2: ...heaters 250 300 400 500 6 5 2 Scheme of the SGW S Maxi water heaters 250 300 400 500 7 5 3 Technical specification of the SGW S Maxi water heaters 700 1000 8 5 4 Scheme of the SGW S Maxi water heater...

Страница 3: ...by warranty 7 Eliminate contamination by using filters to extend the service life of the tank and ensure proper functioning of the relief valve 8 Iftanksoperateinaveryaggressiveenvironment e g inacow...

Страница 4: ...mally insulated If the system operation assumes the usable warm water heating priority using the three way valve we recommend following the installation instructions provided by the manufacturer of th...

Страница 5: ...CORREX and potentiometer plug must not be lengthened 2 A random change in polarity causes the acceleration of corrosion 3 It is recommended to use the socket 230V in a short distance from the tank 4 2...

Страница 6: ...39 Demand for heating water m3 h 3 3 3 3 Dimensions h1 Cold water inflow height mm 130 130 150 180 h2 CH water outflow height mm 215 215 235 265 h3 Sensor cover height mm 385 540 560 610 h4 Circulati...

Страница 7: ...eserved Galmet Sp z o o Sp K Installation and Operating Manual Warranty Card SGW S Maxi Maxi Plus M 7 5 2 Scheme of the SGW S Maxi water heaters 250 300 400 500 d D L h6 h5 h4 h3 h2 h1 0 5 Technical s...

Страница 8: ...0 10 45 C kW 39 39 Demand for heating water m3 h 3 3 Dimensions h1 Cold water inflow height mm 215 245 h2 CH water outflow height mm 395 445 h3 Sensor cover height mm 755 745 h4 CH hot water inflow he...

Страница 9: ...ts reserved Galmet Sp z o o Sp K Installation and Operating Manual Warranty Card SGW S Maxi Maxi Plus M 9 5 4 Scheme of the SGW S Maxi water heaters 700 1000 d D L h6 h5 h4 h3 h2 h1 0 5 Technical spec...

Страница 10: ...m3 h 3 3 3 Dimensions h1 Cold water inflow height mm 130 160 180 h2 CH water outflow height mm 215 245 265 h3 Sensor cover height mm 335 425 410 h4 CH hot water inflow height mm 495 565 645 h5 CH wate...

Страница 11: ...ed Galmet Sp z o o Sp K Installation and Operating Manual Warranty Card SGW S Maxi Maxi Plus M 11 5 6 Scheme of the SGW S Maxi Plus water heaters 300 400 500 d D h8 h7 h5 h3 h2 h1 0 h4 h6 L h9 5 Techn...

Страница 12: ...height mm 210 240 255 h3 Solar water outflow II height mm 290 325 355 h4 Solar sensor cover I height mm 390 475 525 h5 Sensor cover II height mm 490 625 655 h6 Solar water inflow II height mm 670 905...

Страница 13: ...Galmet Sp z o o Sp K Installation and Operating Manual Warranty Card SGW S Maxi Maxi Plus M 13 5 8 Scheme of the SGW S M water heaters 300 400 500 d D h8 h7 h5 h3 h2 h1 0 h4 h6 L h9 h10 h11 h12 5 Tec...

Страница 14: ...SGW S M 300 SGW S M 300 Intended use The water heaters are intended for heating and storage of the DHW The wall thickness of the jackets and the bottoms as well as the material the exchangers were mad...

Страница 15: ...ency class B B C B C C 4 EN Standing loss W 63 65 95 82 106 131 5 EN Storage volume L 236 284 376 471 657 973 7 2 SGW S Maxi Plus 1 EN Supplier s name or trade mark Galmet 2 EN Supplier s model identi...

Страница 16: ...mbleddirectlyinfrontoftheheateronthepipesupplyingitwithcoldwater Onlyvalvesacceptablebyadequateorgansshould beused adjustedtostoragewaterheaters Safetyvalveshouldbeusedaccordingtotheoperatingmanualfor...

Страница 17: ...Themethodforrepairshallbespecifiedbythemanufacturer 21 Multiple repairs will not include the following heater adjustment replacement of magnesium anode replacement of gaskets nor any element wearing d...

Страница 18: ...Notes...

Страница 19: ...f repair Service s seal Service s seal Service s seal Service s seal Owner s name and address Owner s name and address Owner s name and address Owner s name and address Owner s signature Owner s signa...

Страница 20: ...Installation confirmation Type Factory no Date of sale Seller s stamp and signature Warranty coupon 1 Warranty coupon 2 Warranty coupon 3 Warranty coupon 4 Type Type Type Type Factory no Factory no Fa...

Отзывы: