3.2. Installing the heat pump indoors
The heat pump must be installed in such a way to allow a service technician to maintain the compressor unit and should provide access to at least to one wall
of the device. A minimum distance from the wall should be 40 cm. A minimum floor area needed to install the heat pump is 2 x 2 m (4 square meters), while
the room height should be above 50 cm. When installing the device without the ducts carrying the air to the outside of the building - provide a minimum
room ventilation at a level of 300-365 m
3
/h (depending on the model).
A > 500 mm
B > 400 mm
3.3. Heat pump positioned inside the room
Air ducts
Backup room
(e.g. laundry, garage)
CAUTION! The minimum length between the suction duct and cold air outlet should
be at least 1.5 m!
The room needs proper ventilation system, and its capacity should be at least 30 m
3
.