© All rights reserved - Galmet Sp. z o.o. Sp. K
Installation and operation manual of the Basic heat pump
29
3. Installation
3.1. Connection diagram for the heat pump's air ducts
Air inlet
ø 160 mm
Air outlet
ø 160 mm
Max. duct length 5 m
rated air flow of 365 m
3
/h
(varies with model)
Max. duct length 5 m
rated air flow of 365 m
3
/h
(varies with model)
The length of both the outlet and inlet air ducts can not exceed 5 m straight. Each 90° bend shortens the length of the straight air duct
by 2 m. When the recommended length of 5 m is exceeded, it is recommended to use appropriate support fan to assist the flow of air. It is
recommended to use non-corrugated air ducts, as corrugated ones could cause unwanted air resistance.
Remember, that cold air flowing through the air ducts can cause moisture condensation from the air. It is dependant on condintions and air
characteristics insde the room. It is recommended to insulate air ducts.
To avoid mixing different air streams, minimum distance between the suction duct
and air outlet should be 1,5 m!
If the device works using air circulating in the room, then it needs to have proper ventilation system and the room capacity has to be
checked.