7
RG66002124 - Rev 05
All copying, even partial, of this manual is strictly forbidden
MCA
5
TECHNICAL FEATURES
5.2
HEAT PUMPS RATINGS
* Weights referred to version including pump and buffer tank
- Cooling capacity:
outdoor air temperature 35°C, water temperature 12°C / 7°C
- Heating capacity:
outdoor air temperature 7°C dry bulb and 6.2°C wet bulb, water temperature 40°C/45°C
- Sound power level
measured according to standards EN 23741 and EN 29614-1
- Sound pressure level
measured at a distance of 10 m and a height of 1.5 m above the ground in a free field (fan side).
- The maximum electrical input is the mains electricity that must be available in order for the unit to work.
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit. It is the maximum current allowed in the unit.
This value may never be exceeded; it must be used as a reference for determining the size of the power supply line and the related safety devices (refer
to the wiring diagram supplied with the units).
MCA-H
10 M
10
12
14
16
21
25
30
37
50
60
Power supply
V - ph - Hz 230-1-50
Cooling capacity
kW
9,25
9,28
10,77
13,18
16,49
19,30
22,86
30,95
33,90
48,20
58,30
MCA HB Cooling power input
kW
4,20
4,09
5,15
5,84
6,93
8,67
10,26
12,94
15,34
18,70
24,10
MCA HP - HS Cooling power input
kW
4,57
4,47
5,53
6,21
7,30
9,05
10,81
13,49
15,89
19,30
24,70
Heating capacity
kW
11,19
11,13
12,90
16,01
19,62
23,10
26,79
37,52
41,81
57,10
71,40
MCA HB Heating power input
kW
4,10
4,00
4,64
5,56
6,88
8,28
10,05
12,86
14,62
19,60
24,40
MCA HP - HS Heating power input
kW
4,47
4,37
5,01
5,93
7,45
8,66
10,60
13,41
15,17
20,20
25,00
Maximum power input
kW
5,6
5,5
6,5
7,5
9,0
10,7
12,9
16,8
19,0
26,0
36,0
Maximum current absorption
A
28,4
12,4
14,4
16,1
18,4
21,4
28,0
33,0
37,2
44,0
58,0
Starting absorbed current
A
117,4
54,4
69,9
78,4
102,4
134,4
138,0
143,0
183,0
190,0
240,0
n° of scroll compressor / circuits
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
Refrigerant charge
kg
2,6
2,6
2,6
3,4
5,3
6,3
7,8
9,5
13,2
18,0
21,0
Low/high pressure switch
bar
1,4 / 28
1,4 / 28
1,4 / 28
1,4 / 28
1,4 / 28
1,4 / 28
1,4 / 28
1,4 / 28
1,4 / 28
1,4 / 28
1,4 / 28
n° of axial fan
2
2
2
2
2
2
1
1
1
1
1
Air flow
m
3
/h
5580
5580
5580
5040
6300
5800
10750
10620
10501
19000
18000
Water flow in cooling mode
l/s
0,442
0,443
0,514
0,630
0,788
0,922
1,092
1,479
1,620
2,304
2,785
Water flow in heat pump
l/s
0,534
0,532
0,616
0,765
0,937
1,104
1,280
1,793
1,998
2,730
3,410
Diameter of hydrualic connections
"
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
2
2
Water pressure drop (cooling)
kPa
36
37
32
46
32
35
39
36
33
25
24
Water pressure drop (heating)
kPa
52
52
45
67
45
49
52
52
49
33,7
36,0
Available pressure head (cooling)
kPa
155
154
157
138
145
136
134
130
130
81
125
Available pressure head (heating)
kPa
135
136
140
111
125
112
117
107
103
62
95
Water content escluding optionals
dm
3
1
1
1
1
1,5
2
2
3
3
9
10
Expansion tank
dm
3
5
5
5
5
5
5
8
8
8
12
12
Buffer tank
dm
3
30
30
30
30
82
82
125
125
125
210
210
Height
mm
1128
1128
1128
1128
1228
1228
1390
1390
1390
1589
1589
Length
mm
1120
1120
1120
1120
1400
1400
1500
1500
1500
1989
1989
Depth
mm
578
578
578
578
628
628
1050
1050
1050
1202
1202
Sound power level
dB(A)
69
69
70
71
72
74
78
79
80
81
81
Sound pressure level
dB(A)
41
41
42
43
44
46
50
51
52
53
53
Transport weight *
kg
162
162
172
176
235
246
334,5
364
410
665
694
Operating weight *
kg
177
177
187
191
310,5
321,5
449,5
479
524,5
841
880
400-3-50