UNITS’ PERFORMANCE TABLE
FM
22/23
32/33
42/43
Unit
Configuration
Configuration
2-pipe
Number Of Fan Blowers
Single
Power Supply
(V/Ph/Hz)
230/1/50
220/1/60
Operation Control
Complete function onboard PCB with integrated group control
functionality, incl. 1 pc return air sensor and 2 pcs temperature
sensors.
Per
for
mance Data
Air
Total Air Flow
e
H
m
3
/h
500
645
876
M
370
445
740
L
290
370
570
Cooling
Cooling Capacity
e
H
kW
2,17
3,16
4,38
M
1,71
2,36
3,84
L
1,43
2,03
3,12
Sensible Cooling Capacity
e
H
1,59
2,31
3,18
M
1,25
1,71
2,78
L
1,04
1,46
2,24
FCEER
e
Rating
175
192
213
Class
B
A
A
Heating
Heating Capacity
e
H
kW
2,64
3,83
5,25
M
2,08
2,83
4,58
L
1,71
2,44
3,68
FCCOP
e
Rating
211
232
255
Class
B
B
B
Sound
Sound Pressure Level (Outlet)
dB(A)
35/27/24
41/32/27
46/40/34
Sound Power Level (Outlet)
e
46/38/35
52/43/38
57/51/45
Electrical
Fan Motor Power
e
H
W
13
20
30
M
10
13
20
L
8
10
13
Fan Motor Apparent Power @
32
50
83
Fan Motor Running Current @
A
0,142
0,182
0,272
Hydraulic
Cooling Water Flow Rate
H
L/h
370
543
752
M
294
406
658
L
244
348
536
Cooling Pressure Drop
e
H
kPa
12
14,1
19,4
M
8,06
8,58
15,5
L
5,9
6,62
10,8
Heating Water Flow Rate @H/M/L
L/h
Same as “Cooling Water Flow Rate”
Heating Pressure Drop
e
H
kPa
9
12
16
M
4,5
7
13
L
3,5
5
8
Water Content
L
0,0789
0,124
0,192
Constr
uction
and P
acking Data
Water Connections
Type
Socket (Threaded Female)
In
mm [in]
12,70 [1/2]
Out
Condensate Drainage Connection
16 [5/8]
Dimensions
L
mm
876
W
228
H
300
Net Weight
Kg
12
13
14
1.”e” refers to technic
al information listed on the Eurovent website. Eurovent
testing conditions:
a. Cooling mode:
- Return air temperature: 27C DB/ 19C WB.
- Inlet/ outlet water temperature: 7C°/ 12C°.
- Water flow-rate: variable.
b. Heating mode:
- Return air temperature: 20C.
- Inlet water temperature: 50C.
- Water flow-rate: same as 2-pipe cooling.