Technical manual

ACQVARIA

EN

3 - 10 kW

cassette fan coils with On/OFF motor

2

4

Supervision GARDA

2 pipes systems

4 pipes systems Touch screen device Recess ceiling-mount

PLUS

» 

Reliability and sturdiness in a compact design

» 

Fresh air with direct or mixed introduction

» 

Heat exchanger up to 3 rows

» 

Condensate drainage pump for height differences of up 

to 0.9 m

» 

Air intake and diffusion grille in two colors (RAL9010 

and RAL9030)

» 

Reduced installation and commissioning time

WC66000496

03/21

Содержание ACQVARIA AQ10Q0B0

Страница 1: ...device Recess ceiling mount PLUS Reliability and sturdiness in a compact design Fresh air with direct or mixed introduction Heat exchanger up to 3 rows Condensate drainage pump for height differences...

Страница 2: ...nery Directive the Electromagnetic Compatibility Directive the Electrical Safety Directive and the Pressure Equipment Directive Fulfillment of the Ecodesign requirements is fully in keeping with the e...

Страница 3: ...IGHTS p 16 7 PERFORMANCES p 17 8 SOUND LEVELS p 18 9 ELECTRICAL CONNECTION DIAGRAMS p 19 10 OVERALL DIMENSIONS p 31 11 ACCESSORIES p 35 11 1 2 OR 3 WAY MOTOR DRIVEN VALVE KITS p 38 11 2 PRESSURE INDEP...

Страница 4: ...cent rooms The design and colour RAL9003 or RAL9010 of the air intake and diffusion louvre guarantee optimal integration into the sus pended ceiling panels Easy access to the air filter for cleaning o...

Страница 5: ...display MCSUE Humidity sensor for MY COMFORT medium e large EVO MCSWE Water sensor for MYCOMFORT and EVO controllers Electronic microprocessor control panels TED 2T Electronic controller for AC fan co...

Страница 6: ...t 2 4 FAN DRIVE ASSEMBLY Three speed electrical motor directly connected to a centrifu gal fan with backward curving blades with profile optimised for stable operation at all speeds 2 5 CONDENSATE COL...

Страница 7: ...Locking clips 2 Tie rods 3 Condensate drip tray 4 Condensate drainage pump 5 Heat exchanger 6 Fan drive assembly 7 External insulation 8 Internal insulation 9 Lateral sheet metal 10 Sheet metal back 1...

Страница 8: ...Condensate drip tray 4 Condensate drainage pump 5 Heat exchanger 6 Fan drive assembly 7 External insulation 8 Internal insulation 9 Lateral sheet metal 10 Sheet metal back 11 Reinforcement brackets 1...

Страница 9: ...4 5 2 3 6 4 2 5 1 4 2 5 1 5 4 Height Y m 2 0 2 3 2 8 2 0 2 6 3 4 2 4 2 7 3 2 2 3 2 6 3 1 2 6 3 1 3 3 Distance Z m 2 3 2 6 3 1 2 3 2 9 3 9 3 1 3 5 4 1 2 9 3 3 3 9 3 3 3 9 4 2 Air range 4T Model AQ10 AQ...

Страница 10: ...nlight positions exposed to direct currents of warm or cold air placing obstacles that impede an accurate temperature reading NB The water sensor where present must be mounted in the appropriate trap...

Страница 11: ...ement a logic that makes it possible to set a fixed speed between minumum medium and maximum or automatic speed modulation The automatic logic varies the analog signal to the motor be tween minimum me...

Страница 12: ...312 Pay attention to the excess length B of the suspension rod Fig 7 it may interfere with the unit s electrical box Place the fan coil unit in the suspended ceiling orienting the side with the water...

Страница 13: ...WC66000496 All copying even partial of this manual is strictly forbidden 13 Fig 5 AQ 40 50 60 Fig 6 18 8 11 Fig 7 1 Nut washer 2 Washer nut lock nut Fig 8 Fig 9 AQ10 20 Fig 10 AQ40 50 60...

Страница 14: ...ember to at tach it again after installation Lift the grille to remove it from the control panel Fig 11 To install the front panel Fig 12 Turn the two locking clips 5 downwards Attach the control pane...

Страница 15: ...e F A 2 2 2 Fuses type gG ACQVARIA AQ50Q0B0 AQ60Q0B0 Speed min med max min med max Total cooling capacity 1 kW 5 16 6 11 8 24 6 34 8 61 9 73 Sensible cooling capacity 1 kW 3 68 4 37 6 10 4 59 6 40 7 3...

Страница 16: ...rea of power cables 4 mm 1 00 1 00 1 00 1 00 Power supply cable type N07V K Safety fuse F A 2 2 2 2 Fuses type gG 1 Water temperature 7 C 12 C air temperature dry bulb 27 C wet bulb 19 C 47 relative h...

Страница 17: ...etailed report which includes performances dimensional drawings tender specifications and the economic offer Product selection Filters to make the identification of the requested product easier Perfor...

Страница 18: ...4 7 12 0 40 max 54 2 51 9 49 5 45 3 42 0 32 2 19 5 51 AQ60Q0B0 min 44 1 41 8 38 2 35 3 27 7 14 7 12 0 40 med 54 2 51 9 49 5 45 3 42 0 32 2 19 5 51 max 58 0 57 1 53 8 49 8 46 1 39 3 27 2 56 4 pipes ACQ...

Страница 19: ...end Check that the mains electricity supply is compatible with the voltage shown on the unit rating plate 9 1 My Comfort Base wiring diagram for AQ 10 20 M Fanmotor MP Condensate drainage pump FLOAT F...

Страница 20: ...on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor BU M Blue common motor BN FLOA...

Страница 21: ...it breaker not supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor WH M White minimum speed mot...

Страница 22: ...ast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor BU M Blue common motor BN F...

Страница 23: ...Circuit breaker not supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor WH M White minimum spe...

Страница 24: ...supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor BU M Blue comm...

Страница 25: ...hot and cold F 2A fuse not supplied IL Circuit breaker not supplied CN Fast on connector SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor WH...

Страница 26: ...upplied IL Circuit breaker not supplied CN Fast on connector SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor B...

Страница 27: ...hot and cold F 2A fuse not supplied IL Circuit breaker not supplied CN Fast on connector SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor W...

Страница 28: ...supplied IL Circuit breaker not supplied CN Fast on connector SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed motor...

Страница 29: ...fuse not supplied IL Circuit breaker not supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed GY M Grey medium speed motor W...

Страница 30: ...Circuit breaker not supplied CN Fast on connector SU Umidity sensor SW Water temperature sensor SA Room temperature sensor BK M Black maximum speed BU M Blue Medium speed motor RD M Red minimum speed...

Страница 31: ...den 31 10 OVERALL DIMENSIONS 10 1 Dimensional drawing AQ 10 20 2 pipes LEGEND 1 Electric box 2 Condensate discharge 10 3 Water outlet 1 2 female gas 4 Water inlet 1 2 female gas 1 m 1 m 1 m 1 m 614 21...

Страница 32: ...sional drawing AQ 40 50 60 2 pipes LEGEND 1 Electric box 2 Condensate discharge 10 3 Water outlet 3 4 female gas 4 Water inlet 3 4 female gas 1 m 1 m 1 m 1 m 830 830 n 1 1 350 30 793 860 485 860 92 5...

Страница 33: ...es LEGEND 1 Electric box 2 Condensate discharge 10 3 Cooling exchanger water outlet 1 2 gas F 4 Cooling exchanger water inlet 1 2 gas F 5 Heating exchanger water outlet 1 2 gas F 6 Heating exchanger w...

Страница 34: ...ctric box 2 Condensate discharge 10 3 Cooling exchanger water outlet 3 4 gas F 4 Cooling exchanger water inlet 3 4 gas F 5 Heating exchanger water inlet 1 2 gas F 6 Heating exchanger water outlet 1 2...

Страница 35: ...withintheheatexchanger or on the room temperature with a neutral zone that can be selected in the range from 2 to 5 C The controller is equipped with a large display 3 to show and set all the function...

Страница 36: ...onal manual or automatic switch on the basis of air temperature Water consent on the basis of temperature LED503 Recess wall mounted microprocessor control The proposed microprocessor control panels f...

Страница 37: ...OFF servo control it acts directly on the valve shutter Hydraulic plumbing kit made with copper piping and brass connectors VKM 3 way motor driven modulating valve complete with hydraulic kit It cont...

Страница 38: ...in the figures from page p 38 Pressure drops of the valve hydraulic kit assembly are calculated using the following formula PW QW KV 2 Where PW pressure drop in kg cm2 QW water flow rate in m3 h KV w...

Страница 39: ...forbidden 39 3 way valve kit 2 pipes AQ 10 20 1 Water outlet 2 Water inlet NOTE The actuator is not shown 1 3 2 2 way valve kit 4 pipes AQ 10 20 1 Cold water outlet 2 Cold water inlet 3 Hot water outl...

Страница 40: ...kit 4 pipes AQ 10 20 1 Cold water outlet 2 Cold water inlet 3 Hot water outlet 4 Hot water inlet NOTE The actuators are not shown 1 3 2 4 5 2 way valve kit 2 pipes AQ 40 50 60 1 Water outlet 2 Water i...

Страница 41: ...bidden 41 3 way valve kit 2 pipes AQ 40 50 60 1 Water outlet 2 Water inlet NOTE The actuator is not shown 1 3 2 2 way valve kit 4 pipes AQ 40 50 60 1 Cold water outlet 2 Cold water inlet 3 Hot water o...

Страница 42: ...y ON OFF or modulating function total opening time 3 minutes Hydraulic kit with O ring for connection with the exchanger and paper gasket for connection with the valve Brackets for fastening the hydra...

Страница 43: ...l of this manual is strictly forbidden 43 2 way valve kit VPIC 2 pipes AQ 10 20 1 Water outlet 2 Water inlet 1 2 2 way valve kit VPIC 4 pipes AQ 10 20 1 Cold water outlet 2 Cold water inlet 3 Hot wate...

Страница 44: ...cal manual 44 2 way VPIC valve kit 2 pipes AQ 40 50 60 1 Water outlet 2 Water inlet 2 1 2 way VPIC valve kit 4 pipes AQ 40 50 60 1 Cold water outlet 2 Cold water inlet 3 Hot water outlet 4 Hot water i...

Страница 45: ...FOR INTAKE OF FRESH AIR TO BE TREATED The units are equipped with 3 fresh air inlets positioned in the corners This air mixes with the air drawn in from the indoor en vironment and is then treated by...

Страница 46: ...nit must be ther mally insulated to prevent the formation of surface conden sation The following graphs show the air flow values as a function of the pressure drops of the duct at different fan speed...

Страница 47: ...fresh air is introduced into the installation room by passing the heat exchanger by means of a supply fin of the unit The dimensions of diameter D are Model D ACQVARIA 10 20 150 ACQVARIA 40 50 60 180...

Страница 48: ...proceed as follows Figure 21 1 Before performing any work on the unit disconnect it from the power supply 2 Remove the screws 1 securing the retainers 2 on each side 3 To open the grille 3 push on th...

Страница 49: ...g the screws Remove the tank handling it with care Clean the inside of the tank Check that the heat exchanger is clean If needed use a vac uum cleaner with a rubber tip to remove dust being careful no...

Страница 50: ...via Romagnoli 12 a 40010 Bentivoglio BO Italy Ph 39 051 8908111 Fax 039 051 8908122 UNI EN ISO 9001 and UNI EN ISO 45001 www galletti com...