Part Number: 3E2453 R1 |
3
Installation Note | Gallagher T10 Mifare Reader
Cable type
Combined power and data
in a single cable
CAT5e
100m (320ft)
SEC472 (4 x 0.2mm
2
)
100m (320ft)
SEC4142 (4 x 0.4mm
2
)
100m (320ft)
BELDEN 8723 (22 AWG)
152m (500ft)
BELDEN 9842 (24 AWG)
152m (500ft)
Distance between Proximity Readers
The distance separating any two proximity readers must not be less than
200mm (8 inches) in all directions.
200mm
When mounting a proximity reader on an internal wall, check that any
reader fixed to the other side of the wall is not less than 200mm (8 inches)
away.
W
all thickness
less than 200mm
200mm
Installation
The Gallagher T10 Mifare reader is designed to be mounted on any solid
flat surface. However installation on metal surfaces, particularly those with
a large surface area will reduce read range. The extent to which the range
is reduced will depend upon the type of metal used.
The recommended mounting height for the reader is 1.1m (3.6ft) from the
floor level to the centre of the reader device. However this may vary in
some countries and you should check local regulations for variations to this
height.